Table of Anomaly Signals
In case of malfunctioning of the system, the controller switches off the
regulation output and displays the type of anomaly.
For example the controller will signal the breakage of any connected
thermocouple by displaying
(flashing) on display. For other
notifications, see the table below.
#
Cause
What to do
E-01
Error in E²PROM cell
programming
Call Assistance
E-02
Cold junction sensor fault or room
temperature outside of allowed
limits.
Call Assistance
E-04
Incorrect configuration data.
Possible loss of calibration values.
Check if the configuration parameters
are correct.
E-05
Thermocouple open or
temperature outside of limits.
Check the connection with the
sensors and their integrity.