SET COMMUNICATION:
This section defines the fundamental communication parameters of two buses, PROFINET and Modbus.
By Pressing the “
Set Communication
” button from the main window for SW67602 (Fig. 2) the window “Set Communication”
appears (Fig. 3).
The window is divided in two sections, one for the PROFINET and the other for the Modbus Master.
The means of the fields for “PROFINET” are:
In the fields “
IP ADDRESS
” insert the IP address that you want to give to the Converter;
In the fields “
SUBNET
Mask
” insert the Subnet Mask;
In the fields “
GATEWAY
” insert the default gateway that you want to use. This feature can be enabled or disabled pressing
the Check Box field. This feature is used for going out of the net;
In the field “
Port
” is possible to define the port to use for the “Tunneling mode” (see “Advanced functions” section for
more details);
In the field "
PROFINET Name of Station
" is possible to assign a name to the PROFINET node;
In the fields “
Number Byte IN
” insert the number of input byte of the slave station;
In the fields “
Number Byte Out
” insert the number of output byte of the slave station;
In the field “
Diagnostic
” insert the starting byte of the PROFINET array where you will save the diagnostic of Modbus. It is
possible to enable/disable this function using the checkbox.
For more information about the diagnostic, see “Diagnostic” section.
The means of the fields for the “Modbus Master” section are:
In the field “
Serial
” the serial to use is defined (select RS485);
In the field “
Baudrate
” the baudrate for the serial line is defined;
In the field “
Parity
” the parity of the serial line is defined;
In the field “
TimeOut (ms)
” there is the maximum time that the device attends for the answer from the Slave
interrogated;
In the field “
Communication Idle Time (ms)
” the minimun delay between two polls is defined.
Figure 3: “Set Communication” window
Содержание CNV510-PNET-RTU-A
Страница 1: ...pag 1 CNV510 PNET RTU A Software version SW67602 PROFINET Slave Modbus Master Converter User Manual...
Страница 4: ...pag 4 MECHANICAL DIMENSIONS...
Страница 5: ...pag 5 EXAMPLE OF CONNECTION...
Страница 6: ...pag 6 CONNECTION SCHEME...
Страница 7: ...pag 7 POWER SUPPLY...
Страница 25: ...pag 25 5 Load the configuration into the PLC...