pag. 30
B5 command
This command allows to enable/disable the polling to a single Modbus slave.
REQ:
Byte 0
Byte 1
Byte 2
0xB5
Slave ID
0x00/0x01
0x01 = Disable polling for Modbus slave
0x00 = Enable polling for Modbus slave
If the message is received correctly, the same message will be sent back by the converter.
Example:
They are connected 3 Modbus slaves (Modbus IDs 1, 2, 3) to the converter and we want to stop the polling to the slave with ID = 2.
The message to send to the converter will be:
Byte 0
Byte 1
Byte 2
0xB5
0x02
0x01