Table of Anomaly Signals
If installation malfunctions, the controller switches off the regulation output and reports the anomaly
noticed. For example, controller will report failure of a connected thermocouple visualizing
e-05
(flashing) flashing on display.
For other signals see table below.
Cause
What to do
E-02
SYSTEM
Error
Cold junction temperature sensor failure or
environment temperature out of range
Call assistance
E-04
eeprom
Error
Incorrect configuration data.
Possible loss of instrument calibration
Verify that configuration parameters are
correct.
E-05
PRobe 1
Error
Sensor connected to AI1 broken or
temperature out of range
Control connection with probes and their
integrity.
E-06
PRobe 2
Error
Sensor connected to AI2 broken or
temperature out of range
Control connection with probes and their
integrity.
E-08
SYSTEM
Error
Missing calibration
Call assistance
E-10
a.in.2
disabled
Analogue input 2 disabled but used during
configuration.
Enable
A.in.2
or disable it during configura-
tion.
E-80
rfid Error
Tag rfid malfunctioning
Call assistance
Notes / Updates
1 Display of decimal point depends on setting of parameter
sen.
and parameter
d.p.
2 On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm condition reappers, after that
it was restored.