28 - ATR244 -
User manual
GROUP B -
A.in.2
- Analogue input 2
18
SEN.2
Sensor AI2
Analogue input configuration / sensor AI2 selection
diSab.
Disabled
Disabled. (
Default
)
tc. k
Tc-K
-260 °C..1360 °C.
tc. s
Tc-S
-40 °C..1760 °C
tc. r
Tc-R
-40 °C..1760 °C
tc. J
Tc-J
-200 °C..1200 °C
Tc. T
Tc-T
-260 °C..400 °C
tc. E
Tc-E
-260 °C..980 °C
tc. N
Tc-N
-260 °C..1280 °C
tc. b
Tc-B
100 °C..1820 °C
Pt100
Pt100
-200 °C..600 °C
ni100
Ni100
-60 °C..180 °C
ntc
NTC 10K
-40 °C..125 °C
Ptc
PTC 1K
-50 °C..150 °C
Pt500
Pt500
-200 °C..600 °C
Pt1k
Pt1000
-200 °C..600 °C
0-1
0..1 V
0-5
0..5 V
0-10
0..10 V
0-20
0..20 mA
4-20
4..20 mA
0-60
0..60 mV
Pot.
PPotentiometer (set the value on parameter 23)
19
d.P. 2
Decimal Point 2
Select number of displayed decimal points for AI 2
0
Default
0.0
1 decimal
0.00
2 decimals
0.000
3 decimals
20
rEs.
Reserved
Reserved parameter.
21
L.L.i.2
Lower Linear Input AI2
AI2 lower limit only for linear signals. Ex.: with input 4..20 mA this parameter takes value associated
to 4 mA. The value may be greater than the one entered on the next parameter.
-9999..+30000
[digit
1 p. 65
]
Default
: 0.
22
u.L.i.2
Upper Linear Input AI2
AI2 upper limit only for linear signals Ex: with input 4..20 mA this parameter takes value associated
to 20 mA.The value may be lower than the one entered on the previous parameter..
-9999..+30000
[digit
1 p. 65
]
Default
:1000
23
P.vA.2
Potentiometer Value AI2
Selects the value of the potentiometer connected on AI2
1..150 kohm
.
Default
: 10kohm
24
i.o.L.2
Linear Input over Limits AI2
If AI2 is a linear input, allows to the process to overpass the limits (Par. 18 and 19).
diSab.
Disabled (
Default
)
Enab.
Enabled