50 - ATR244 -
User manual
217
A.6.o.t.
Alarm 6 Output Type
Defines the output type if the alarm 6 is analogue.
0.10 v
Output 0...10 V.
Default
4.20ma
Output 4...20 mA.
218
a.6.Hy.
Alarm 6 Hysteresis
Alarm 6 hysteresis
-9999..+9999 [digit
1 p. 65
] (degrees.tenths for temp. sensors).
Default
0.5.
219
A.6.L.L.
Alarm 6 Lower Limit
Lower limit selectable for the alarm 6 setpoint.
-9999..+30000 [digit
1 p. 65
] (degrees for temp. sensors).
Default
0.
220
A.6.u.L.
Alarm 6 Upper Limit
Upper limit selectable for the alarm 6 setpoint.
-9999..+30000 [digit
1 p. 65
] (degrees for temp. sensors).
Default
1750.
221
a.6.re.
Alarm 6 Reset
Alarm 6 contact reset type.
A. rEs.
Automatic reset (
Default
)
M. rEs.
Manual reset (manual reset by keyboard or by digital input)
M.rEs.S.
Stored manual reset (keeps the output status also after a power failure)
222
A.6.S.e.
Alarm 6 State Error
Alarm 6 output status in case of error.
If the alarm output is 0-10V:
0 V
0 V.
Default
10 v
10 V.
If the alarm output is 0-20 mA or 4-20 mA:
0 ma
0 mA.
Default
4 ma
4 mA.
20 ma
20 mA.
21.5ma
21.5 mA.
223
rES.
Reserved
Reserved parmeter
224
a.6.de.
Alarm 6 Delay
Alarm 6 Delay.
-3600..+3600 seconds.
Default
: 0.
Negative value: delay when exit alarm status
Positive value: delay when enter alarm status
225
A.6.S.p.
Alarm 6 Setpoint Protection
Allows or not to change the alarm 6 setpoint.
FrEE
Editable by the user (
Default
)
Lock
Protected
HidE
Protected and not visualized
226
A.6.Lb.
Alarm 6 Label
Selects the message to be visualized in case of alarm 6 intervention
0
Disabled .
Default
0.
1-20
Message 1..20 (see customizable messages table)
227÷230
Reserved Parameters - Group L
Reserved parameters - Group L