- ATR227 - User manual

10.d 

Lower Deviation Alarm (

L.d.aL.

 selection)

1

Pv

Comand Spv

Alarm Spv

Off

Off

On

On

Hysteresis

parameter



 > 0

Time

Alarm

output

Alarm Spv

Lower deviation alarm value of alarm

setpoint greater than “0” and hysteresis

value greater than “0” (Par.29 

A.1.HY.

 > 0).**

2

Pv

Comand Spv

Alarm Spv

Off

Off

Hysteresis

parameter



 > 0

Time

Alarm

output

Comand Spv

Comand Spv

Comand Spv

Comand Spv

Alarm Spv

Alarm Spv

Lower deviation alarm value of alarm

setpoint less than “0” and hysteresis

value greater than “0” (Par.29 

A.1.HY.

 > 0).**

**  a) The example refers to alarm 1; the function can also be enabled for alarm 2    .b) With hysteresis value less 

than “0” (

A.1.HY.

 < 0)  the dotted line moves over the alarm setpoint.

11  Table of Anomaly Signals

If installation malfunctions, controller will switch off  regulation output and report 

the anomaly. For example, controller will report failure of a connected thermocouple 

visualizing 

e-05

 (fl ashing) on display 1 and 

prb.

 (sensor) on display 2. For other signals, 

see table below.

Cause

What to do

E-01

EEP.E

Error in EEPROM cell programming.

Call Assistance.

E-02

SYS.E

Cold junction sensor fault or room 

temperature outside of allowed limits. Call Assistance.

E-03

MEM.E

Error in Memory card programming.

Repeat Memory card programming.

E-04

EEP.E

Incorrect confi guration data.

Possible loss of calibration values.

Check if the confi guration parameters 

are correct.

E-05

prb.

Thermocouple open or temperature 

outside of limits.

Check the connection with the 

sensors and their integrity.

E-08

SYS.E

Missing calibration data.

Call Assistance.

Содержание ATR227 Series

Страница 1: ...ATR227 Controller User manual...

Страница 2: ......

Страница 3: ...ts Led 10 6 3 Keys 11 7 Controller Functions 11 7 1 Modifying Main Setpoint and Alarm Setpoint Values 11 7 2 Auto Tuning 11 7 3 Manual Tuning 11 7 4 Automatic Tuning 12 7 5 Soft Start 12 7 6 Automatic...

Страница 4: ...4 ATR227 Manuale d uso...

Страница 5: ...wed to use the device and or service it and in accordance to technical data and environmental conditions listed in this manual Do not dispose electric tools together with household waste material In o...

Страница 6: ...ld junction accuracy 0 1 C C Impedence 0 10 V Ri 110 k 0 20 mA Ri 50 4 20 mA Ri 50 0 60 mV Ri 500 k Relay outputs 2 relays Configurable as command and or alarm output Contacts 2 A 250 V Resistive load...

Страница 7: ...ts please observe following safety guidelines Separate control line from power wires Avoid proximity of remote control switches electromagnetic contactors powerful engines and use specific filters Avo...

Страница 8: ...at one side only For thermoresistances PT100 Ni100 For the three wire connection use wires with the same section For the two wire connection short circuit terminals 1 and 3 When shielded cable is used...

Страница 9: ...ERNAL SUPPLY ALIMENTAZIONE ESTERNA A 1 For linear signals 0 4 20 mA with external power supply for sensor Comply with polarity A Sensor output B Sensor ground 6 12V 30mA 4 20mA V A C PRESSURE TRANSMIT...

Страница 10: ...1 1234 Normally displays the process During configuration phase it displays the parameter being entered 2 1234 Normally displays the setpoint During configuration phase it displays the parameter value...

Страница 11: ...ease or decrease main setpoint 2 SET Visualizes alarm setpoint on display 1 3 cor d Value on display 2 changes Increase or decrease the alarm setpoint value 7 2 Auto Tuning Tuning procedure to calcula...

Страница 12: ...e using the same procedure select auto on display 2 MAN led switches off and functioning backs to auomatic 2 Second selection en st enables the same functioning but with two important variants If ther...

Страница 13: ...ter 43 o cL t as follows 7 9 a tiME Time control For this type of control it is suggested to use a zero crossing SSR Activation and deactivation of the output is related to the time selected on parame...

Страница 14: ...on advanced Burst fire firing mode reduces the brightness of the infrared elements and thus minimises annoying visual flickering In a short wave infrared application advanced Burst fire firing mode re...

Страница 15: ...s 5 SET cor d Increase or decrease the visualized value pressing SET and an arrow key Enter the new data which will be saved on releasing the keys To change another parameter return to point 4 6 c d t...

Страница 16: ...Ni100 60 C 180 C ntc NTC10K 40 C 125 C Ptc PTC1K 50 C 150 C Pts Pt500 100 C 600 C Pt 1k Pt1000 100 C 600 C 0 10 0 10 V 0 20 0 20 mA 4 20 4 20 mA 0 60 0 60 mV Pot 1 Potenziometri fino a 6 kOhm Pot 2 Po...

Страница 17: ...nual tune or tune once once Once P I D parameters calculation only once at starting Man Manual P I D automatic parameters calculation by keyboard 9 Lo L S Lower Limit Setpoint Password 1234 999 9999 d...

Страница 18: ...I D functioning are Automatic Reset Default mre Manual Reset mre s Manual Reset Stored keeps relay status also after an eventual power failure 18 c de Command Delay Password 5678 Command delay only in...

Страница 19: ...m 1 selection dis Disabled Default A AL Absolute threshold referring to process b AL Band alarm H d AL Upper deviation alarm L d AL Lower deviation alarm 28 A I 5 o Alarm 1 State Output Password 1234...

Страница 20: ...int free Modifiable by the user Default Lock Locked Hide Locked and hidden 33 a1 re Alarm 1 Reset Password 5678 Type of Reset for contact of alarm 1 are Automatic Reset Default mre Manual reset by key...

Страница 21: ...State Error Password 5678 State of contact for alarm 2 output in case of error o c Open contact Default c c Closed contact 40 a 2 sp Alarm 2 Setpoint Protection Password 1234 Does not allow the user...

Страница 22: ...ted 10 0 90 0 Default 80 0 46 L L P P Lower Limit Phase Angle Percentage Password 5678 Select the min value for the command output with Phase Angle control 0 40 Default 10 47 u L P P Upper Limit Phase...

Страница 23: ...tpoint for the threshold used by autotuning to calculate the P I D parameters 0 0 500 0 C F Default 30 0 56 m G tu Max Gap Tune Password 5678 Selects the max process setpoint gap beyond which the auto...

Страница 24: ...s parameter 0 Time Alarm output Absolute alarm with controller in heating functioning Par 7 Act t selected Heat and hysteresis value less than 0 Par 29 A 1 HY 0 3 Off On On Off Hysteresis parameter 0...

Страница 25: ...ers to alarm 1 the function can also be enabled for alarm 2 10 c Upper Deviation Alarm H d aL selection 1 Pv Comand Spv Alarm Spv Off Off On On Hysteresis parameter 0 Time Alarm output Alarm Spv Coman...

Страница 26: ...er the alarm setpoint 11 Table of Anomaly Signals If installation malfunctions controller will switch off regulation output and report the anomaly For example controller will report failure of a conne...

Страница 27: ...in sequence to configure inputs control output or retransmission of signal 2200 PT100 100 500 C ON OFF with hysteresis 1 C on Q1 absolute Alarm 1 on Q2 2201 PT100 100 500 C ON OFF with hysteresis 1 C...

Страница 28: ...re Command Reset Password 5678 18 18 c de Command Delay Password 5678 18 19 au ma Automatic Manual Password 1234 18 21 Sft G Softstart Gradient Password 5678 18 24 S tim Softstart Time Password 5678...

Страница 29: ...sword 5678 22 48 p b Proportional Band Password 5678 22 49 i t Integral Time Password 5678 22 50 d t Derivative Time Password 5678 22 51 d b Dead Band Password 5678 22 52 c t Cycle Time Password 5678...

Страница 30: ...sing connecting the device Prima di utilizzare il dispositivo leggere con attenzione le informazioni di sicurezza e settaggio contenute in questo manuale PIXSYS s r l www pixsys net sales pixsys net s...

Отзывы: