User manual - ATR227 -
23
52
c.t.
Cycle Time (Password 5678)
(for P.I.D. on remote control switch 15 sec., for P.I.D. on SSR 1 sec.)
1-300 seconds (
Default
:15s) If par.6
c.out
is set as
c.SSr
, (
Default
:2s).
53
L.L.o.P.
Lower Limit Output Percentage (Password 5678)
Selects min. value for command output percentage
0..100%,
Default
: 0%.
54
U.L.o.p.
Upper Limit Output Percentage (Password 5678)
Selects max. value for command output percentage
0 – 100
%,
Default
: 100%.
55
s.d.tu.
Setpoint Deviation Tune (Password 5678)
Selects the deviation from the command setpoint for the threshold used by
autotuning to calculate the P.I.D. parameters
0.0-500.0°C/°F.
Default
: 30.0.
56
m.G.tu.
Max Gap Tune (Password 5678)
Selects the max. process-setpoint gap beyond which the automatic tune
recalculates PID parameters
0.1..50.0°C/°F.
Default:
1.0°C
57
mn.p.b.
Minimum Proportional Band (Password 5678)
Selects the min. proportional band value selectable by the automatic tune.
0.0..100.0°C/°F.
Default: 5
.0°C
58
ma.p.b.
Maximum Proportional Band (Password 5678)
Selects the max. proportional band value selectable by the automatic tune.
0.0..300.0°C/°F.
Default:
50.0°C
59
mn.i.t.
Minimum Integral Time (Password 5678)
Selects the min. integral time value selectable by the automatic tune.
0.0..999.9 secondi.
Default
: 40.0s.