ATR401 - User manual
39
32
Derivative
Time
Normally ¼ of integral time.
0.0…999.9 seconds. 0 derivative disabled,
Default
: 0.0.
33
Cycle
Time
Cycle time (for P.I.D. on remote control switch 10 / 15 sec., for P.I.D. on SSR
1 sec.) or servo time (value declared by servo-motor manufacturer).
0.1…300.0 seconds,
Default
: 10.0.
34
Lower Limit Output Percentage
Select minimum value for command output percentage.
0…100%,
Default
: 0%.
Example: with
selected as 0...10 V and
set at 10%, command
output can change from a min. of 1 V to a max. of 10 V.
35
Upper Limit Output Percentage
Selects maximum value for command output percentage.
0…100%,
Default
: 100%.
Example:
selected as 0...10 V and
selected as 90%,
command output may vary between 0V and max. 9 V
36
Degree
Select degree type.
Centigrade
(
Default
)
Fahrenheit
37
Alarm
1
Alarm 1 selection. Alarm intervention is correlated to AL1.
Disabled
(
Default
)
Absolute alarm, referring to process
Band
alarm
Upper deviation alarm
Lower deviation alarm
Absolute alarm, referring to command setpoint
Status alarm (active in Run / Start)
Cooling
action
Load control alarm (Heater Break Alarm)
Sensor failure alarm (Loop Break Alarm)
Example: status of contactor/ SSR or heating elements