34
ATR401 - User manual
3
Decimal Point 1
Select type of visualized decimal point for Analogue Input 1.
Default
1
decimal
2
decimals
3
decimals
4
Lower Linear Input
AI1 lower range limit only for linear signals. Example: with input 4...20 mA
this parameter takes value associated to 4 mA.
-999…+9999 digit
3
,
Default
: 0.
5
Upper Limit Input 1
AI1 upper range limit only for linear signals. Example: with input 4...20 mA
this parameter takes value associated to 20 mA.
-999…+9999 digit
3
,
Default
: 1000.
6
Off set Calibration 1
Off set AI1 calibration. Value added/subtracted to visualized process value
(normally used to correct ambient temperature value)
-999…+1000 digit
3
for linear sensors and potentiometers.
-99.9…+100.0 tenths for temperature sensors,
Default
: 0.0.
7
Gain Calibration 1
AI1 gain calibration. % Value multiplied with displayed value to calibrate
process value.
-99.9%…+100.0%,
Default
: 0.0.
Example: to correct a scale 0...1000°C which is showing 0...1010°C, enter
-1.0 on this parameter
8
Latch-On
1
Automatic setting of limits for linear input.
Disabled
(
Default
)
Standard
Virtual Zero Stored (see paragraph 8.9)
Virtual Zero Initialized (see paragraph 8.9)