ATR401 - User manual
13
Lower Linear Input 2
AI2 lower range limit only for linear signals. Example: with input 4...20 mA
this parameter takes value associated to 4 mA.
-999…+9999 digit
4
,
Default
: 0.
14
Upper Linear Input 2
AI2 upper range limit only for linear signals. Example: with input 4...20 mA
this parameter takes value associated to 20 mA
-999…+9999 digit
4
,
Default
: 1000.
15
Off set Calibration 2
AI2 off set calibration. Number added to visualized process value (normally
correcting ambient temperature value).
-999…+1000 digit
4
for linear sensors and potentiometers.
-99.9…+100.0 tenths for temperature sensors,
Default
: 0.0.
16
Gain Calibration 2
AI2 Gain calibration. % Value multiplied with displayed value to calibrate
process value.
-99.9%…+100.0%,
Default
: 0.0.
17
Lower Limit Setpoint 2
AI2 lower limit setpoint.
-999…+9999 digit
4
(degrees i f temperature),
Default
: 0.
18
Upper Limit Setpoint 2
AI2 upper limit setpoint.
-999…+9999 digit
4
(degrees i f temperature),
Default
: 1750.
19
Command
Process
Selects process value related to command output and visualized on
display 1. This determinates which is the primary process
Process 1 (
Default
)
Process
2
Process
mean
Processes
diff erence
Processes diff erence as absolute value
AI1+AI2 Input addition
4
The display of the decimal point depends on the setting of parameter
. and
or
and