ATR401 - User manual
27
Modbus
address
Descrizione
Read Write
Reset
value
5
Slave address
R/W
EEPROM
6
Boot version
RO
EEPROM
50
Automatic addressing
WO
-
51
Installation code comparison
WO
-
500
Loading Default values:
9999
Restore all values
9998
Restore all values except for baud-rate
and slave address
9997
Restore all values except for baud-rate
9996
Restore all values except for slave
address
R/W
0
900
Process AI1 (degrees with tenths of degree for
temperature sensors; digits for linear sensors)
RO
-
901
Process AI2 (degrees with tenths of degree for
temperature sensors; digits for linear sensors)
RO
-
902
Average AI1-AI2 (degrees with tenths of
degree for temperature sensors; digits for
linear sensors)
RO
-
903
Diff erence AI1-AI2 (degrees with tenths of
degree for temperature sensors; digits for
linear sensors)
RO
-
904
Diff erence AI1-AI2
as absolute value (degrees
with tenths of degree for temperature sensors;
digits for linear sensors)
RO
-
905
Addition AI1-AI2 (degrees with tenths of
degree for temperature sensors; digits for
linear sensors)
RO
-
1000
Command process (degrees with tenths of
degree for temperature sensors; digits for
linear sensors)
RO
-
1001 Setpoint 1
R/W
EEPROM
1002 Setpoint 2
R/W
EEPROM
1003 Setpoint 3
R/W
EEPROM
1004 Setpoint 4
R/W
EEPROM
1005 Alarm 1
R/W
EEPROM