User manual -
ATR171 43
12.b
Absolute Alarm or Threshold Alarm Referring to Setpoint
Command
(selection
a.c.AL.
)
1
Absolute alarm refers to the command set,
with the controller in heating functioning
(par. 17
act.t.
selected
Heat
)
hysteresis
value greater
than “0 (par. 36
a.1.Hy.
> 0).
Command set can be changed by pressing
the arrow keys on front panel. *
12.c
Band Alarm (selection
b. aL.
)
1
Band alarm with hysteresis value greater
than “0”. (par. 36
a.1.Hy.
> 0). *
2
Band alarm with hysteresis value minor
than “0”. (par. 36
a.1.Hy.
< 0). *
* a) The example refers to alarm 1; the function can also be enabled for alarm 2 and 3 on models that include
it.