13 Table of Anomaly Signals
If installation malfunctions, controller will switch off regulation output and will
report the anomaly. For example, controller will report failure of a connected
thermocouple visualizing
e-05
(flashing) flashing on display.
For other signals see table below.
Cause
What to do
E-01
SYS.E.
EEPROM programming error.
Call assistance.
E-02
SYS.E.
Cold junction temperature
sensor failure or environment
temperature out of range.
Call assistance.
E-04
SYS.E.
Incorrect configuration data.
Possible loss of instrument
calibration.
Verify that configuration
parameters are correct.
E-05
PRo.1
Sensor connected to AI1 broken or
temperature out of range.
Control connection with probes
and their integrity.
E-06
PRo.2
Sensor connected to AI2 broken or
temperature out of range.
Control connection with probes
and their integrity.
E-08
SYS.E.
Missing calibration.
Call Assistance.
E-10
c.pa.r
Incorrect control parameters.
Verify control parameters.
E-11
a.pa.r
Incorrect alarms parameters.
Verify alarm parameters.
E-12
r.pa.r
Incorrect retransmission
parameters.
Verify retransmission parameters.
E-13
u.pa.r
Incorrect visualization parameters. Verify visualization parameters.
E-14
s.pa.r
Incorrect remote setpoint
parameters.
Verify remote setpoint parameters.
Notes / Updates