32 ATR171 -
User manual
27
t.i.
Integral Time
Process inertia in seconds
0.0..999.9 seconds. 0 integral disabled,
Default
: 0
28
t.d.
Derivative Time
Normally ¼ of integral time.
0.0..999.9 seconds. 0 derivative disabled,
Default
: 0
29
t.c.
Cycle Time
Cycle time (for P.I.D. on remote control switch 10 / 15 sec., for P.I.D. on SSR 1 sec.)
or servo time (value declared by servo-motor manufacturer).
0.1..300.0 seconds,
Default
: 10
30
L.L.o.p.
Lower Limit Output Percentage
Select minimum value for command output percentage.
0..100%,
Default
: 0%.
Example: with
c.out
selected as 0...10 V and
L.L.o.p
set at 10%, command output
can change from a min. of 1 V to a max. of 10 V.
31
u.L.o.p.
Upper Limit Output Percentage
Selects maximum value for command output percentage.
0..100%,
Default
: 100%.
Example:
c.out
selected as 0...10 V and
u.L.o.p.
selected as 90%, command
output may vary between 0V and max. 9 V
32
deGr.
Degree
Select degree type.
c
Centigrade (
Default
)
f
Fahrenheit
33
AL. 1
Alarm 1
Alarm 1 selection. Alarm intervention is correlated to AL1
(See par. 12)
dis.
Disabled (
Default
)
a. aL.
Absolute alarm, referring to process
b. aL.
Band alarm
H.d.aL.
Upper deviation alarm
L.d.aL.
Lower deviation alarm
a.c.AL.
Absolute alarm, referring to command setpoint
st.Al.
Status alarm (active in Run / Start)
cooL.
Cooling action
t.run
Timer run
t.end
Timer end
Содержание ATR 171