
1. Indoor Unit Combination
Multi DC
Outdoor Unit
Nominal
capacity
Suggested
Combination
Limit
DUAL ZONE
(18K Nominal)
5.2kW
9
None
12
9+9
9+12
12+12(*)
Multi DC
Outdoor Unit
Nominal
capacity
Suggested
Combination
Limit
TRIPLE ZONE
(27K Nominal)
7.5kW
9
There should be
only one Floor
Ceiling or Duct
unit.
12
18
9+9
9+12
9+18
12+12
12+18
9+9+9
9+9+12
9+12+12
12+12+12(*)
Multi DC
Outdoor Unit
Nominal
capacity
Suggested
Combination
Limit
TRIPLE ZONE
(30K Nominal)
8.0kW
9
There should be
only one Floor
Ceiling or Duct
unit.
12
18
9+9
9+12
9+18
12+12
12+18
18+18
9+9+9
9+9+12
9+9+18
9+12+12
9+12+18
12+12+12
Multi DC
Outdoor Unit
Nominal
capacity
Suggested
Combination
Limit
QUAD ZONE
(36K Nominal)
10.5kW
9
None
12
18
9+9
9+12
9+18
12+12
12+18
18+18
9+9+9
9+9+12
9+9+18
9+12+12
9+12+18
9+18+18
12+12+12
12+12+18
12+18+18
9+9+9+9
9+9+9+12
9+9+9+18
9+9+12+12
9+9+12+18
9+12+12+12
9+12+12+18
12+12+12+12
(*): NOTICE: This combination results in slightly reduced
performance. We recommend going one size up for the
outdoor section for obtaining fully rated performance.
Содержание YN018GMFI16M2D
Страница 19: ...7 Wiring Diagrams 8 1 Wiring diagram of DUAL Circuit outdoor unit YN018GMFI16M2D ...
Страница 20: ...PCB board of YN018GMFI16M2D ...
Страница 21: ...IPM board of YN018GMFI16M2D ...
Страница 22: ...8 2 Wiring diagram of Triple Circuit outdoor unit YN027GMFI16M3D YN030GMF16M3D ...
Страница 23: ...PCB board of YN030GMFI16M3D ...
Страница 24: ...IPM board of YN030GMFI16M3D ...
Страница 25: ...PCB board of YN027GMFI16M3D ...
Страница 26: ...IPM board of YN027GMFI16M3D ...
Страница 27: ...8 3 Wiring diagram of Quadruple 4 zone outdoor unit YN036GMFI16M4D ...
Страница 28: ...PCB board of YN036GMFI16M4D ...
Страница 29: ...IPM board of YN036GMFI16M4D ...
Страница 30: ...PFC board of YN036GMFI16M4D ...
Страница 46: ......
Страница 48: ...9 4 1 7 Over voltage or too low voltage protection diagnosis and solution ...
Страница 60: ...IPM for dual tri zone IPM for quad zone P N for dual tri zone ...
Страница 61: ...P N for quad zone ...
Страница 62: ...bridge rectifier for dual tri zone bridge rectifier for quad zone ...
Страница 63: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Страница 65: ...Two ports of the inductance Inductance ...
Страница 66: ......
Страница 71: ......
Страница 73: ......
Страница 75: ......
Страница 77: ......
Страница 89: ...6 EXV check Disconnect the connectors ...
Страница 91: ...Red Blue Red Yellow ...
Страница 92: ...Brown Orange Brown White ...
Страница 108: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Страница 116: ...Screws of big handle Screws of right rear panel Screws of water collector Screws of terminal board ...
Страница 122: ...10 Exploded Views Available under a separate document file ...