Heating mode:
Current
frequency(Hz)
Current limit
value(A)
Frequency limit
HEAT_F16
IHEATLMT12 Decrease the frequency to
HEAT_F4 and run at HEAT_F4 for
3 minutes.
After that, the frequency will be
adjusted according to the capacity
demand and rise to the upper
level every 3 minutes
(When the frequency>Heat_F4 via
capacity demand).
HEAT_F15
IHEATLMT11
HEAT_F14
IHEATLMT10
HEAT_F13
IHEATLMT9
HEAT_F12
IHEATLMT8
HEAT_F11
IHEATLMT7
HEAT_F10
IHEATLMT6
HEAT_F9
IHEATLMT5
HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will
not be limited.
After 10s of the compressor start, if the current>IHEAT, the AC will
display the failure for 30 seconds and stop. The AC will restart 3
minutes later.
7.3.7 Indoor / outdoor unit communication
protection
If the indoor units cannot receive the feedback
signal from the outdoor unit for 2 minutes, the
system will stop and display the failure.
7.3.8 High condenser coil temp. protection.
When T3>65
℃
for 3 seconds, the compressor
will stop while the indoor fan and outdoor fan will
continue running.
When T3<52
℃
, the protection will reset and the
compressor will restart after 3 minutes.
7.3.9 Outdoor unit anti-freezing protection
When T2B<0
℃
for 250 seconds, the indoor unit
capacity demand will be set as zero and reset to
normal when T2B>10
℃
.
7.3.10 Oil return
Running rules:
1.If the compressor frequency stays lower than
RET_OIL_FREQ1_ADD for
RET_OIL_TIME1_ADD, the system will rise the
running frequency to RET_OIL_FREQ2_ADD for
RET_OIL_TIME2_ADD and then resume back to
former frequency.
2.During the oil return process, the EXV will stay
at 300p setting while the indoor units will keep the
current running mode.
7.3.11 Compressor preheating functions
----Preheating permitting condition:
If T4 (outdoor ambient temperature)
<
3
℃
when
newly powered on or if T4
<
3
℃
and compressor
had stopped for over 3 hours, the compressor
heating cable will be activated.
----Preheating mode:
A weak current flows through the windings of the
compressor through its wiring terminal, then the
compressor stays heated while it is off.
----Preheating release condition:
If T4
>
5
℃
or the capacity demand isn’t zero,
preheating function will stop.
7.3.12 Compressor crankcase heater
----Preheating permitting condition:
①
When T4<3
℃
within 5 seconds of being
plugged in, the crankcase heater will be
active.
②
When T4<3
℃
and the compressor is not
running for 3 hours, the crankcase heater will
be active.
----Preheating release condition:
When T4
≧
5
℃
or the indoor has any capacity
demand, the crankcase heater will stop working.
Содержание YN018GMFI16M2D
Страница 19: ...7 Wiring Diagrams 8 1 Wiring diagram of DUAL Circuit outdoor unit YN018GMFI16M2D ...
Страница 20: ...PCB board of YN018GMFI16M2D ...
Страница 21: ...IPM board of YN018GMFI16M2D ...
Страница 22: ...8 2 Wiring diagram of Triple Circuit outdoor unit YN027GMFI16M3D YN030GMF16M3D ...
Страница 23: ...PCB board of YN030GMFI16M3D ...
Страница 24: ...IPM board of YN030GMFI16M3D ...
Страница 25: ...PCB board of YN027GMFI16M3D ...
Страница 26: ...IPM board of YN027GMFI16M3D ...
Страница 27: ...8 3 Wiring diagram of Quadruple 4 zone outdoor unit YN036GMFI16M4D ...
Страница 28: ...PCB board of YN036GMFI16M4D ...
Страница 29: ...IPM board of YN036GMFI16M4D ...
Страница 30: ...PFC board of YN036GMFI16M4D ...
Страница 46: ......
Страница 48: ...9 4 1 7 Over voltage or too low voltage protection diagnosis and solution ...
Страница 60: ...IPM for dual tri zone IPM for quad zone P N for dual tri zone ...
Страница 61: ...P N for quad zone ...
Страница 62: ...bridge rectifier for dual tri zone bridge rectifier for quad zone ...
Страница 63: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Страница 65: ...Two ports of the inductance Inductance ...
Страница 66: ......
Страница 71: ......
Страница 73: ......
Страница 75: ......
Страница 77: ......
Страница 89: ...6 EXV check Disconnect the connectors ...
Страница 91: ...Red Blue Red Yellow ...
Страница 92: ...Brown Orange Brown White ...
Страница 108: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Страница 116: ...Screws of big handle Screws of right rear panel Screws of water collector Screws of terminal board ...
Страница 122: ...10 Exploded Views Available under a separate document file ...