9.3 Outdoor Unit Display
9.3.1 Outdoor unit error code function
There is a system check switch on the outdoor PCB.
Push the switch SW1 to check the status of unit when the unit is running. The digital display will display
the codes based on the following procedures, after pushing the SW1 each time.
Display
Remark
0
Normal display
Display running frequency, running state or malfunction code
1
No. of indoor units in good connection
Actual data
Display Number of indoor unit
1
1
2
2
3
3
4
4
2
Outdoor unit running mode code
Off:0,Fan only 1, Cooling:2, Heating:3, Forced cooling:4
3
A indoor unit capacity
The capacity unit is horse power. If the indoor unit is not connected, the digital
display digits will show: “――”
(9K:1HP,12K:1.2HP,18K:1.5HP)
4
B indoor unit capacity
5
C indoor unit capacity
6
D indoor unit capacity
7
E indoor unit capacity (Not Applicable!)
SW1
Содержание YN018GMFI16M2D
Страница 19: ...7 Wiring Diagrams 8 1 Wiring diagram of DUAL Circuit outdoor unit YN018GMFI16M2D ...
Страница 20: ...PCB board of YN018GMFI16M2D ...
Страница 21: ...IPM board of YN018GMFI16M2D ...
Страница 22: ...8 2 Wiring diagram of Triple Circuit outdoor unit YN027GMFI16M3D YN030GMF16M3D ...
Страница 23: ...PCB board of YN030GMFI16M3D ...
Страница 24: ...IPM board of YN030GMFI16M3D ...
Страница 25: ...PCB board of YN027GMFI16M3D ...
Страница 26: ...IPM board of YN027GMFI16M3D ...
Страница 27: ...8 3 Wiring diagram of Quadruple 4 zone outdoor unit YN036GMFI16M4D ...
Страница 28: ...PCB board of YN036GMFI16M4D ...
Страница 29: ...IPM board of YN036GMFI16M4D ...
Страница 30: ...PFC board of YN036GMFI16M4D ...
Страница 46: ......
Страница 48: ...9 4 1 7 Over voltage or too low voltage protection diagnosis and solution ...
Страница 60: ...IPM for dual tri zone IPM for quad zone P N for dual tri zone ...
Страница 61: ...P N for quad zone ...
Страница 62: ...bridge rectifier for dual tri zone bridge rectifier for quad zone ...
Страница 63: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Страница 65: ...Two ports of the inductance Inductance ...
Страница 66: ......
Страница 71: ......
Страница 73: ......
Страница 75: ......
Страница 77: ......
Страница 89: ...6 EXV check Disconnect the connectors ...
Страница 91: ...Red Blue Red Yellow ...
Страница 92: ...Brown Orange Brown White ...
Страница 108: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Страница 116: ...Screws of big handle Screws of right rear panel Screws of water collector Screws of terminal board ...
Страница 122: ...10 Exploded Views Available under a separate document file ...