Plus all the indoor capacity requests together,
then modify it by T4
When there is only one indoor unit
Heating
Outdoor temperature (T4)
<
0
℃
<
12
℃
12
℃
~ 17
℃
≥17
℃
Modify rate
120%
80%
40%
20%
When there are more than one indoor units
Heating
Outdoor temperature (T4)
<
0
℃
<
12
℃
12
℃
~ 17
℃
≥17
℃
Modify rate
120%
100%
80%
60%
Note: The final result is integer.
Then modify it according to T2 average
(correction):
Note: Average value of T2
:
Sum T2 value of all
indoor units / indoor units number
According to the final capacity request to
confirm the operating frequency, as per the
following table.
Frequency
(Hz)
0
HEAT
_F1
HEAT
_F2
…
HEAT
_F15
HEAT
_F16
Amendatory
capacity
demand.
0
1
2
…
15
16
Heating capacity improvement in low ambient
heating
In heating mode, when
T2<T2_ExitT4LowFre_ADD , and T4<-4
℃
,
there’s frequency elevation:
elevated frequency= Recent frequency * 110%
When T2> T2_ExitT4LowFre_ADD-2 and T4>-6,
the highest frequency can’t exceed F17
When T2> T2_ExitT4LowFre_ADD-4 and T4>-8,
the highest frequency can’t exceed F18
When T2> T2_ExitT4LowFre_ADD-6 and T4>-10,
the highest frequency can’t exceed F19
For all other conditions, the highest frequency is
F20
7.4.2 Defrost control
Condition of defrosting:
T3
≦
TempEnterDefrost_ADD
℃
and lasts for 40
minutes.
Defrosting action
:
off
on
Cool
‐
F9
10S 30S
TimeA
10S
4
‐
way
valve
defrosting
Defrosting
over
compressor
Indoor
fan
Outdoor
fan
EXV
open
frequency
Max
10
minutes
frequency
Compressor
stops
off
Anti
‐
cold
control
off
480P
480P
for
240s
Condition of ending defrost mode:
If any one of following items is satisfied,
defrosting will stop and the system will switch to
normal heating mode.
①
T3 > TempQuitDefrost_ADD
℃
;.
②
The defrosting time reaches 10min.
③
Turning any other modes on or off.
Содержание YN018GMFI16M2D
Страница 19: ...7 Wiring Diagrams 8 1 Wiring diagram of DUAL Circuit outdoor unit YN018GMFI16M2D ...
Страница 20: ...PCB board of YN018GMFI16M2D ...
Страница 21: ...IPM board of YN018GMFI16M2D ...
Страница 22: ...8 2 Wiring diagram of Triple Circuit outdoor unit YN027GMFI16M3D YN030GMF16M3D ...
Страница 23: ...PCB board of YN030GMFI16M3D ...
Страница 24: ...IPM board of YN030GMFI16M3D ...
Страница 25: ...PCB board of YN027GMFI16M3D ...
Страница 26: ...IPM board of YN027GMFI16M3D ...
Страница 27: ...8 3 Wiring diagram of Quadruple 4 zone outdoor unit YN036GMFI16M4D ...
Страница 28: ...PCB board of YN036GMFI16M4D ...
Страница 29: ...IPM board of YN036GMFI16M4D ...
Страница 30: ...PFC board of YN036GMFI16M4D ...
Страница 46: ......
Страница 48: ...9 4 1 7 Over voltage or too low voltage protection diagnosis and solution ...
Страница 60: ...IPM for dual tri zone IPM for quad zone P N for dual tri zone ...
Страница 61: ...P N for quad zone ...
Страница 62: ...bridge rectifier for dual tri zone bridge rectifier for quad zone ...
Страница 63: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Страница 65: ...Two ports of the inductance Inductance ...
Страница 66: ......
Страница 71: ......
Страница 73: ......
Страница 75: ......
Страница 77: ......
Страница 89: ...6 EXV check Disconnect the connectors ...
Страница 91: ...Red Blue Red Yellow ...
Страница 92: ...Brown Orange Brown White ...
Страница 108: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Страница 116: ...Screws of big handle Screws of right rear panel Screws of water collector Screws of terminal board ...
Страница 122: ...10 Exploded Views Available under a separate document file ...