2

installation manual

To  guarantee  proper  installation,  please  first  read  this 
"installation manual" in its entirety.

The air conditioner must be installed by qualified persons.

When installing the indoor unit or its tubing, please follow 
this manual as strictly as possible.

If  the  air  conditioner  is  installed  on  a  metallic  part  of  the 
building,  it  must  be  electrically  insulated  according  to  the 
relevant standards for electrical appliances.

When all of the installation work is finished, please turn on 
the power only after a thorough inspection is performed.

This  handbook  guarantees  succesful  system  operation. 
However, future manuals will contain the latest information.

2.    INSTALLATION INFORMATION

Ground the air conditioner.

Do  not  connect  the  ground  wire  to  gas  or  water  pipes, 
lightning  rods,  or  telephone  ground  wires.  Incomplete 
grounding may result in electric shocks.

Be sure to install an earth leakage breaker.

Failure  to  install  an  earth  leakage  breaker  may  result  in 
electrical shocks.

Connect  the  outdoor  unit  wires  before  connecting  the 
indoor unit wires.

 

You are not permitted to connect the air conditioner with the 
power source until the wiring and piping for the air conditioner 
is completed.

When  following  the  instructions  in  this  installation 
manual,  be  sure  to  install  drain  piping  to  ensure  proper 
drainage,  and  insulate  piping  in  order  to  prevent 
condensation.

Improper  or  lack  of  drain  piping  may  result  in  water  leakage 
and property damage.

Install the indoor and outdoor units, power supply wiring, 
and  connecting  wires  at  least  1  meter  away  from  any 
televisions or radios, in order to prevent possible image 
interference or noise.

Depending on the radio waves, a distance of 1 meter may not 
be sufficient enough to eliminate the noise.

This appliance is not intended for use by young children, 
or infirm persons, without supervision.

Don't install the air conditioner in the following locations:

Anywhere that contains unsealed petrolatum.

Areas with salt-saturated air (such as near the coast).

Areas with caustic gas (sulfide, for example) existent 

in the air (such as near a hot spring).

Areas  with  fluctuations  in  incoming  power  supply  (or 
unstable  power  where  the  voltage  fluctuates).  This  can 
happen  in  some  factories  where  some  large  machinery 
can cause noise ion power lines.

In buses or cabinets.

In kitchens that contain gas or oil.

Areas with electromagnetic waves.

Areas with inflammable gases or other materials.

Anywhere near evaporating acids or alkaline liquids.

Any locations undergoing special delicate conditions.

If  the  refrigerant  leaks  during  installation,  ventilate  the 
area immediately.

Toxic  gas  may  be  produced  if  the  refrigerant  comes  into 
contact, whether direct or indirect, with fire.

Since  the  temperature  of  the  refrigerant  circuit  will  be 
high,  please  keep  the  interconnection  cable  away  from 
the copper tube.

After  completion  of  all  installation  work,  check  that  the 
refrigerant does not leak.

Toxic  gas  may  be  produced  if  the  refrigerant  leaks  into  the 
room and comes into contact with a fire source, such as a fan 
heater, stove, or cooker.

INSTALLATION ORDER

Select the location

Install the indoor unit

Install the outdoor unit

Install the connecting pipe 

Connect the drain pipe

Complete all wiring

Test the system operation

CAUTION

The  appliance  shall  be  installed  in  accordance  with 
national wiring regulations.

Do not operate your air conditioner in a wet room, such 
as a bathroom or laundry room.

An all-pole disconnection device, which has at least 3mm 
clearances  in  all  poles,  and  has  a  leakage  current  that 
may exceed 10mA, and the residual current device (RCD) 
having  a  rated  residual  operating  current  not  exceeding 
30mA,  with  disconnection,  must  be  incorporated  in  the 
fixed wiring, in accordance with all relevant wiring laws.

Содержание YN009GMFI22RPD

Страница 1: ...NOTICE Please read this manual carefully before installing or operating your new air conditioning system Be sure to save this manual for your future reference Installation Manual UAB UYB Series Flex Mount UAB Cooling Only Version UYB Cooling and Heating Version Inverter and Inverter Models 18 000 48 000 BTU hr ...

Страница 2: ...If used as a part of a MULTI Split System please refer to the Installation Operation manuals packed with the multi split outdoor unit ...

Страница 3: ...low For electrical work follow all local and national wiring standards and regulations as well as these installation instructions An independent circuit and single outlet must be used If the electrical circuit capacity is insufficient or there is a defect in the electrical work it will cause electrical shock fire Use the specified cable and connect tightly and clamp the cable so that no external f...

Страница 4: ...ended for use by young children or infirm persons without supervision Don t install the air conditioner in the following locations Anywhere that contains unsealed petrolatum Areas with salt saturated air such as near the coast Areas with caustic gas sulfide for example existent in the air such as near a hot spring Areas with fluctuations in incoming power supply or unstable power where the voltage...

Страница 5: ... some spare items please store them carefully aside QUANTITY SHAPE NAME 5 Owner s Manual 6 Installation Manual 7 Remote Controller Manual 1 Remote Controller on some models 2 Remote Controller Holder on some models 4 Alkaline Dry Batteries AM4 1 1 2 2 1 1 Remote Controller Its Holder Others 3 Mounting Screw ST2 9 10 C H 1 ...

Страница 6: ... the unit take into account the following Fragile handle the unit with care Keep the unit upright in order to avoid compressor damage Pre determine the path along which the unit is to be brought in Move and carry this unit without changing its original packaging position by as much as possible When lifting the unit always use protectors to prevent belt damage and pay special attention to the posit...

Страница 7: ...on Inlaying or embedding the screw bolts Install the hanging hook with expanding bolt into the concrete 45 50mm deep to prevent loosening Remove the side board and the grille Refer to Fig 5 8 Side Board Grille Hanging Arm Hanging Screw Bolt 20mm 3 4 In Unit Dimensions 5 3 Table 5 1 unit mm Fig 5 10 Fig 5 11 Fig 5 12 D Connecting Point of Refrigerant Pipe D Gas Side Drain point Downward declivity b...

Страница 8: ...door and indoor unit must not exceed the maximum allowable pipe length If possible DO NOT install the unit where it will be exposed to direct sunshine If possible make sure the unit is located far away from your neighbors property so that the noise from the unit will not cause a disturbance for them If the location is exposed to strong winds for example near a seaside the unit must be placed again...

Страница 9: ...sions W x H x D Mounting Dimensions Distance A Distance B 770x555x300 30 3x21 9x11 8 549 21 6 325 12 8 946x810x410 37 24x31 9x16 14 673 26 5 403 15 87 952x1333x415 37 5x52 5x16 34 634 24 96 404 15 9 845x702x363 33 27x27 6x14 3 540 21 26 350 13 8 800x554x333 31 5x21 8x13 1 514 20 24 340 13 39 YN048GMFI17RUD YN036GMFI17RUD 946x810x410 37 24x31 9x16 14 673 26 5 403 15 87 YN024GMFI22RPD YN018GMFI22RPD...

Страница 10: ... the protective wall cuff inside the hole This protects the edges of the hole and will help seal it when you finish the installation process NOTE The minimum distance between the outdoor unit and walls described in the installation guide does not apply to airtight rooms Be sure to keep the unit unobstructed in at least two of the three vectors M N P See Fig 6 10 CAUTION The drain pipe of the indoo...

Страница 11: ...Pipe Length and Elevation Ensure that the length of the refrigerant pipe the number of bends and the drop height between the indoor and outdoor units meets the requirements shown inTable 8 1 Table 8 1 The Maximum Length And Drop Height Based on Models Unit m ft Type of Model Capacity Btu hr Length of piping Maximum drop height 50Hz T1 Condition R22 Split Type 12K 15 49 8 26 18K 24K 30 98 4 10 32 8...

Страница 12: ... perfect 90 angle Refer to Fig 8 1 for examples of bad cuts Oblique Rough Warped 90 Fig 8 1 Step 2 Remove burrs Burrs can affect the air tight seal of the refrigerant piping connection They must be completely removed 1 Hold the pipe at a downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Pointe...

Страница 13: ... to tighten the flare nut according to the torque values in table 8 2 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Fig 8 7 CAUTION Be sure to wrap insulation around the piping Direct contact with the bare piping mayresult in burns or frostbite Make sure the pipe is properly connected Over tightening may damage the bell mouth and under tightenin...

Страница 14: ... and LIQUID Valves 1 Connect the blue low side hose of the manifold gauge to service port on the outdoor unit s GAS SIDE valve use a 1 4 to 5 16 port adapter if needed which is sold separately 2 Connect yellow middle or common hose from the manifold gauge to the vacuum pump MC MC Fig 6 1 Air and foreign matter in the refrigerant circuit BLUE Low Pressure Side of Manifold Gauge RED High Pressure Si...

Страница 15: ...th the LIQUID side and GAS side Service Calves 13 Tighten valve caps on all three valves service port Liquid Side Gas Side by hand Then tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it seats against the stopper Do not try to force the valve to open further Note on Adding Refrigerant ADDITIONAL REFRIGERANT PER PIP...

Страница 16: ... on the power until you have carefully checked everything after wiring The power cord type designation is H07RN F 2 The Outdoor Unit Check a Whether there are any vibrations or abnormal noises during operation b Whether the generated wind noise or condensation from the air conditioner create any local disturbances c Whether any of the refrigerant has leaked After restarting a protection feature pr...

Страница 17: ...15 installation manual ...

Страница 18: ...ales agency or manufacturer for details 16122700000004 20171209 is a registered trademark of Parker Davis HVAC International Inc Parker Davis HVAC International Inc 2250 NW 102 Place Doral FL 33172 USA Tel 305 513 4488 Fax 305 513 4499 email info pd hvac com Website www pd hvac com Copyright 2017 Parker Davis HVAC International Inc All rights reserved ...

Отзывы: