11
installation manual
6.
Place flaring tool onto the form.
7.
Turn the handle of the flaring tool clockwise until
the pipe is fully flared. Flare the pipe in accordance
with the dimensions shown in table 8-2.
Table 8.2: PIPING EXTENSION BEYOND FLARE FORM
Pipe
Gauge
Tightening
torque
Flare dimension (A)
(Unit: mm/Inch)
Flare shape
Min.
Max.
Ø 1/4
14.2-17.2 N.m
(10.5-12.5 Lb.Ft.)
8.3/0.3
8.3/0.3
R0.4~0.8
5
4
°±
2
90
°±
4
A
Fig. 8.5
Ø 3/8
32.7-39.9 N.m
(24-29.5 Lb.Ft.)
12.4/0.5
12.4/0.5
Ø 1/2
49.5-60.3 N.m
(36.5-44.5 Lb.Ft.)
15.4/0.6
15.8/0.6
Ø 5/8
61.8-75.4 N.m
(45.5-55.5 Lb.Ft.)
18.6/0.7
19/0.74
Ø 3/4
97.2-118.6 N.m
(71.5-87.5 Lb.Ft.)
22.9/0.9
23.3/0.91
8.
Remove the flaring tool and flare form, then inspect
the end of the pipe for cracks and even flaring.
Step 4: Connect the Pipes
Connect the copper pipes to the indoor unit first, then
connect to the outdoor unit. You should first connect the
low-pressure pipe, then the high-pressure pipe.
1.
When connecting the flare nuts, apply a thin coat
of refrigeration oil to the flared ends of the pipes.
2.
Align the center of the two pipes that you will
connect.
Indoor Unit Tubing
Flare Nut
Pipe
Fig. 8.6
3.
Tighten the flare nut as tightly as possible by hand.
4.
Using a spanner, grip the nut on the unit’s tubing.
5.
While firmly gripping the nut, use a torque wrench
to tighten the flare nut according to the torque
values in table 8.2.
NOTE:
Use both a spanner and a torque wrench when
connecting or disconnecting pipes to/from the unit.
Fig. 8.7
CAUTION
• Be sure to wrap insulation around the piping. Direct
contact with the bare piping may result in burns or
frostbite.
• Make sure the pipe is properly connected. Over-
tightening may damage the bell mouth, and under-
tightening may lead to leakage.
NOTE ON MINIMUM BEND RADIUS
Carefully bend the tubing in the middle, according to the
diagram below.
DO NOT
bend the tubing by more than
90°, or more than 3 times.
Bend the pipe with thumbs
Min. radius:10cm (3.9”)
Fig. 8.8
6.
After connecting the copper pipes to the indoor
unit, wrap the power cable, signal cable, and the
piping together with binding tape.
NOTE: DO NOT
intertwine signal cable with other wires.
While bundling these items together , do not intertwine
or cross the signal cable with any other wiring.
7.
Thread this pipeline through the wall, and connect
it to the outdoor unit.
8.
Insulate all the piping, including the valves of the
outdoor unit.
9.
Open the stop valves of the outdoor unit to start
the flow of the refrigerant between the indoor and
outdoor unit.
C AUTION
Check to make sure there is no refrigerant leak after
completing the installation work. If there is a refrigerant
leak, ventilate the area immediately, and evacuate
the system (refer to the Air Evacuation section of this
manual).
Ø 7/8
109.5-133.7 N.m
(80-90 Lb.Ft.)
27/1.06
27.3/1.07
Содержание YN009GMFI22RPD