14

installation manual

10.    WIRING

Link the connective cables to the terminals, as identified with 
their  respective  mached  numbers  on  the  terminal  block  of 
indoor and outdoor units.

Re-install the cover or the protection board.

Connect the Cable

10.1

Remove the electric cover of the outdoor unit. 
If there is no cover on the outdoor unit, disassemble 
the bolts f rom the maintenance board and  remove the 

protection board. (See Fig. 10.1, 10.2)

Cover

Screw

Fig. 10.1

Fig. 10.2

NOTE:

Remark per EMC Directive 2004/108/EC.

To prevent flicker impressions during the start of the compressor 
(technical process), following installation conditions apply: 

1. The power connection for the air conditioner has to be done at 
    the main power distribution. The distribution has to be of a low 
    impedance, normally the required impedance is reached at a
    32A fusing point.

2. No other equipment should be connected with this power line.

3. For detailed installation exceptions, please refer to your power 
    supplier, to confirm if restrictions apply for products like washing 
    machines, air conditioners or electrical ovens. 

4. For power details of the air conditioner refer to the rating plate 
    of the product. 

5. For any other questions, please contact your local dealer.

The appliance shall be installed in accordance with national 
wiring regulations.

The air conditioner should use an independent power 
supply with a properly-rated voltage.

The external power supply to the air conditioner should 
have ground wiring, which is linked to the ground wiring 
of the indoor and outdoor unit.

The wiring work should be done by qualified persons, 
and done according to circuit drawing.

An all-pole disconnection device which has at least 3mm 
separation distance in all-pole, and a residual current 
device (RCD) with a rating of above 10mA, shall be 
incorporated in the fixed wiring, according  to the national
rules.

Be sure to locate the power wiring and the signal wring
well to avoid cross-disturbance.

Do not turn on the power until you have carefully checked 
everything after wiring.

The power cord type designation is H07RN-F. 

2) The Outdoor Unit. Check:
a.  Whether  there  are  any  vibrations  or  abnormal  noises 
during operation.
b.  Whether  the  generated  wind,  noise,  or  condensation 
from the air conditioner create any local disturbances.
c. Whether any of the refrigerant has leaked. 

After  restarting,  a  protection  feature  prevents  the  air 
conditioner from being activated for approximately 3 minutes 
after shut off.

CAUTION

1) The Indoor Unit. Check:
a. Whether the switch on the remote controller works well.
b. Whether the buttons on the remote controller work well.
c. Whether the air flow louver moves normally.
d. Whether the room temperature is adjusted well.
e. Whether the indicator lights work normally.
f. Whether the temporary buttons work well.
g. Whether the drainage is normal.
h.  Whether  there  is  vibration  or  abnormal  noise  during 
operation.
I. Whether the air conditioner heats well, in the case of the 
HEATING/COOLING type.

4

Set the air conditioner to "COOLING" mode with the remote 
controller,  and  check  the  following  points.  If  there  are  any 
malfunctions,  please  resolve  it  according  to  the  chapter 
"Troubleshooting" in the "Owner's Manual". 

Test the operation.

11.  TEST OPERATION

The  test  operation  must  be  carried  out  after  the  entire 
installation has been completed.

Please confirm the following points before the test operation:

2

1

According  to  the  user's  requirements,  install  the  remote 
controller  frame  in  a  place  where  the  remote  controller's 
signal can reach the indoor unit easily.

3

The  power  voltage  fits  the  rated  voltage  of  the  air 
conditioner.
There is no obstacle at the outlet and inlet of the outdoor 
and indoor units.
The gas-side and liquid-side stop valves are both opened.
The air conditioner is pre-heated by turning on the power.

The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The  length  of  the  tubing  and  the  added  stow  capacity  of 
the refrigerant have been recorded.

Содержание YN009GMFI22RPD

Страница 1: ...NOTICE Please read this manual carefully before installing or operating your new air conditioning system Be sure to save this manual for your future reference Installation Manual UAB UYB Series Flex Mount UAB Cooling Only Version UYB Cooling and Heating Version Inverter and Inverter Models 18 000 48 000 BTU hr ...

Страница 2: ...If used as a part of a MULTI Split System please refer to the Installation Operation manuals packed with the multi split outdoor unit ...

Страница 3: ...low For electrical work follow all local and national wiring standards and regulations as well as these installation instructions An independent circuit and single outlet must be used If the electrical circuit capacity is insufficient or there is a defect in the electrical work it will cause electrical shock fire Use the specified cable and connect tightly and clamp the cable so that no external f...

Страница 4: ...ended for use by young children or infirm persons without supervision Don t install the air conditioner in the following locations Anywhere that contains unsealed petrolatum Areas with salt saturated air such as near the coast Areas with caustic gas sulfide for example existent in the air such as near a hot spring Areas with fluctuations in incoming power supply or unstable power where the voltage...

Страница 5: ... some spare items please store them carefully aside QUANTITY SHAPE NAME 5 Owner s Manual 6 Installation Manual 7 Remote Controller Manual 1 Remote Controller on some models 2 Remote Controller Holder on some models 4 Alkaline Dry Batteries AM4 1 1 2 2 1 1 Remote Controller Its Holder Others 3 Mounting Screw ST2 9 10 C H 1 ...

Страница 6: ... the unit take into account the following Fragile handle the unit with care Keep the unit upright in order to avoid compressor damage Pre determine the path along which the unit is to be brought in Move and carry this unit without changing its original packaging position by as much as possible When lifting the unit always use protectors to prevent belt damage and pay special attention to the posit...

Страница 7: ...on Inlaying or embedding the screw bolts Install the hanging hook with expanding bolt into the concrete 45 50mm deep to prevent loosening Remove the side board and the grille Refer to Fig 5 8 Side Board Grille Hanging Arm Hanging Screw Bolt 20mm 3 4 In Unit Dimensions 5 3 Table 5 1 unit mm Fig 5 10 Fig 5 11 Fig 5 12 D Connecting Point of Refrigerant Pipe D Gas Side Drain point Downward declivity b...

Страница 8: ...door and indoor unit must not exceed the maximum allowable pipe length If possible DO NOT install the unit where it will be exposed to direct sunshine If possible make sure the unit is located far away from your neighbors property so that the noise from the unit will not cause a disturbance for them If the location is exposed to strong winds for example near a seaside the unit must be placed again...

Страница 9: ...sions W x H x D Mounting Dimensions Distance A Distance B 770x555x300 30 3x21 9x11 8 549 21 6 325 12 8 946x810x410 37 24x31 9x16 14 673 26 5 403 15 87 952x1333x415 37 5x52 5x16 34 634 24 96 404 15 9 845x702x363 33 27x27 6x14 3 540 21 26 350 13 8 800x554x333 31 5x21 8x13 1 514 20 24 340 13 39 YN048GMFI17RUD YN036GMFI17RUD 946x810x410 37 24x31 9x16 14 673 26 5 403 15 87 YN024GMFI22RPD YN018GMFI22RPD...

Страница 10: ... the protective wall cuff inside the hole This protects the edges of the hole and will help seal it when you finish the installation process NOTE The minimum distance between the outdoor unit and walls described in the installation guide does not apply to airtight rooms Be sure to keep the unit unobstructed in at least two of the three vectors M N P See Fig 6 10 CAUTION The drain pipe of the indoo...

Страница 11: ...Pipe Length and Elevation Ensure that the length of the refrigerant pipe the number of bends and the drop height between the indoor and outdoor units meets the requirements shown inTable 8 1 Table 8 1 The Maximum Length And Drop Height Based on Models Unit m ft Type of Model Capacity Btu hr Length of piping Maximum drop height 50Hz T1 Condition R22 Split Type 12K 15 49 8 26 18K 24K 30 98 4 10 32 8...

Страница 12: ... perfect 90 angle Refer to Fig 8 1 for examples of bad cuts Oblique Rough Warped 90 Fig 8 1 Step 2 Remove burrs Burrs can affect the air tight seal of the refrigerant piping connection They must be completely removed 1 Hold the pipe at a downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Pointe...

Страница 13: ... to tighten the flare nut according to the torque values in table 8 2 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Fig 8 7 CAUTION Be sure to wrap insulation around the piping Direct contact with the bare piping mayresult in burns or frostbite Make sure the pipe is properly connected Over tightening may damage the bell mouth and under tightenin...

Страница 14: ... and LIQUID Valves 1 Connect the blue low side hose of the manifold gauge to service port on the outdoor unit s GAS SIDE valve use a 1 4 to 5 16 port adapter if needed which is sold separately 2 Connect yellow middle or common hose from the manifold gauge to the vacuum pump MC MC Fig 6 1 Air and foreign matter in the refrigerant circuit BLUE Low Pressure Side of Manifold Gauge RED High Pressure Si...

Страница 15: ...th the LIQUID side and GAS side Service Calves 13 Tighten valve caps on all three valves service port Liquid Side Gas Side by hand Then tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it seats against the stopper Do not try to force the valve to open further Note on Adding Refrigerant ADDITIONAL REFRIGERANT PER PIP...

Страница 16: ... on the power until you have carefully checked everything after wiring The power cord type designation is H07RN F 2 The Outdoor Unit Check a Whether there are any vibrations or abnormal noises during operation b Whether the generated wind noise or condensation from the air conditioner create any local disturbances c Whether any of the refrigerant has leaked After restarting a protection feature pr...

Страница 17: ...15 installation manual ...

Страница 18: ...ales agency or manufacturer for details 16122700000004 20171209 is a registered trademark of Parker Davis HVAC International Inc Parker Davis HVAC International Inc 2250 NW 102 Place Doral FL 33172 USA Tel 305 513 4488 Fax 305 513 4499 email info pd hvac com Website www pd hvac com Copyright 2017 Parker Davis HVAC International Inc All rights reserved ...

Отзывы: