Operating Manual PZE X4VP4
1003205-EN-08
16
Example
}
Inductive load: 2 A
}
Utilisation category AC15
}
Contact service life: 400 000 cycles
Provided the application to be implemented requires fewer than 400 000 cycles, the PFH
value (see Technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.
Remove plug-in terminals
Procedure: Insert the screwdriver into the housing recess behind the terminal and lever the
terminal out.
Do
not
remove the terminals by pulling the cables!
Order reference
Type
Features
Connection type
Order no.
PZE X4VP4
24 V DC
tv: 1 - 4 s, selectable
Screw terminals, plug-in
777586
PZE X4VP4 C
24 V DC
tv: 1 - 4 s, selectable
Spring-loaded terminals,
plug-in
787586