background image

PZE X4VP4

Operating Manual PZE X4VP4
1003205-EN-08

9

}

Do not switch low currents using contacts that have been used previously with high cur-
rents.

}

The power supply must comply with the regulations for extra low voltages with protect-
ive electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.

}

Ensure the wiring and EMC requirements of IEC 60204-1 are met.

Preparing for operation

Supply voltage

AC

DC

A1

A2

PZE

24 V DC

0 V

Input circuit

Single-channel

Dual-channel

Base unit:
Safety relay PNOZ X

Driven via safety contacts

A1

A2

PZE

24 V DC

0 V

Feedback loop

Base unit: Safety relay PNOZ X

Y1 and Y2 are inputs on the base
unit; they evaluate the feedback
loop

Setting the delay time

Содержание PZE X4VP4

Страница 1: ...PZE X4VP4 Operating Manual 1003205 EN 08 Safety relays...

Страница 2: ...umentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Interne...

Страница 3: ...ty and liability 6 Disposal 6 For your safety 6 Unit features 7 Safety features 7 Block diagram terminal configuration 7 Function description 8 Installation 8 Wiring 8 Preparing for operation 9 Operat...

Страница 4: ...larly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measur...

Страница 5: ...chnical details see Technical details 11 NOTICE EMC compliant electrical installation The product is designed for use in an industrial environment The product may cause interference if installed in ot...

Страница 6: ...warranty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to not having followed the guidelines in the manual O...

Страница 7: ...nder module expands an existing circuit As the output relays are monitored via the base unit s feedback loop the safety functions on the existing circuit are transferred to the contact expander module...

Страница 8: ...the delay time has elapsed NOTICE At the latest the safety contacts open after the set delay time tv 50 of the set value even in the case of a component failure Installation The unit should be install...

Страница 9: ...separation SELV PELV in accordance with VDE 0100 Part 410 Ensure the wiring and EMC requirements of IEC 60204 1 are met Preparing for operation Supply voltage AC DC A1 A2 PZE 24 V DC 0 V Input circui...

Страница 10: ...tacts of channel 2 are closed Faults Interference By closing or interrupting the input circuit you can check whether the unit switches on or off correctly For safety reasons the unit cannot be started...

Страница 11: ...ind DC DC Voltage tolerance 15 10 15 10 Output of external power supply DC 2 5 W 2 5 W Residual ripple DC 20 20 Duty cycle 100 100 Max inrush current impulse Current pulse A1 1 7 A 1 7 A Pulse duratio...

Страница 12: ...4 V 24 V Max current 4 A 4 A Utilisation category in accordance with UL Voltage 240 V AC G U same polarity 240 V AC G U same polarity With current 5 A 5 A Voltage 24 V DC Resistive 24 V DC Resistive W...

Страница 13: ...60947 5 1 EN 61000 6 2 EN 61326 3 1 Vibration In accordance with the standard EN 60068 2 6 EN 60068 2 6 Frequency 10 55 Hz 10 55 Hz Amplitude 0 35 mm 0 35 mm Airgap creepage In accordance with the sta...

Страница 14: ...ded terminals Terminal points per connection 2 Stripping length with spring loaded terminals 8 mm Dimensions Height 94 mm 101 mm Width 45 mm 45 mm Depth 121 mm 121 mm Weight 300 g 300 g Where standard...

Страница 15: ...is only valid if the values in the service life graphs are met The PFH value depends on the switching frequency and the load on the relay output If the service life graphs are not accessible the state...

Страница 16: ...ust be provided on all output contacts With capacitive loads any power surges that occur must be noted With DC con tactors use flywheel diodes for spark suppression Remove plug in terminals Procedure...

Страница 17: ...ucts meet the requirements of the directive 2006 42 EC for ma chinery of the European Parliament and of the Council The complete EC Declaration of Conformity is available on the Internet at www pilz c...

Страница 18: ...p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document dependin...

Отзывы: