PZE X4VP4
Operating Manual PZE X4VP4
1003205-EN-08
13
Times
777586
787586
Delay time tv
1 s, 2 s, 3 s, 4 s
1 s, 2 s, 3 s, 4 s
Time accuracy
-50 %/+50 %
-50 %/+50 %
Supply interruption before de-ener-
gisation
500 ms
500 ms
Environmental data
777586
787586
Climatic suitability
EN 60068-2-78
EN 60068-2-78
Ambient temperature
Temperature range
-10 - 55 °C
-10 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
-40 - 85 °C
Climatic suitability
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Not permitted
EMC
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
Vibration
In accordance with the standard
EN 60068-2-6
EN 60068-2-6
Frequency
10 - 55 Hz
10 - 55 Hz
Amplitude
0,35 mm
0,35 mm
Airgap creepage
In accordance with the standard
EN 60947-1
EN 60947-1
Overvoltage category
III / II
III / II
Pollution degree
2
2
Rated insulation voltage
250 V
250 V
Rated impulse withstand voltage
4 kV
4 kV
Protection type
Mounting area (e.g. control cab-
inet)
IP54
IP54
Housing
IP40
IP40
Terminals
IP20
IP20
Mechanical data
777586
787586
Mounting position
Any
Any
Mechanical life
10,000,000 cycles
10,000,000 cycles
Material
Bottom
PPO UL 94 V0
PPO UL 94 V0
Front
ABS UL 94 V0
ABS UL 94 V0
Top
PPO UL 94 V0
PPO UL 94 V0
Connection type
Screw terminal
Spring-loaded terminal
Mounting type
plug-in
plug-in