Wiring
Operating Manual PSSu E S 2AI I se(-T)
21417-EN-04
31
}
On base modules with screw terminals:
– If you use a multi-strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
2
, Form A or C,
although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.
– Maximum torque setting: 0.8 Nm
}
Use copper wiring.
6.2
Terminal configuration
Base module
Terminal configuration
Screw terminals:
PSSu BP 1/8 S
PSSu BP 1/8 S-T
Cage clamp terminals:
PSSu BP 1/8 C
PSSu BP 1/8 C-T
Without C-rail:
11: Input I0
21: Input I1
12-22: 0 V analogue
(12-22 linked within the base
module)
13-23: Shield connection
(13-23 linked within the base
module)
14: Not connected
24: Not connected
21
11
22
12
23
13
24
14