Messages
A module error is displayed via the "Err" LED (see section entitled "Display elements"). It is
signalled to the head module and then entered in the
}
Error stack, with PSSu in system environment A
}
Diagnostic log, with PSSu in system environment B.
of the head module.
The module can detect the following errors:
Errors
Explanation
Remedy
Start-up error
Error as the PSSu system starts
up
Change faulty module.
Configuration error
Incorrect module type configured. The configured hardware registry
does not match the actual hard-
ware registry.
ST communication error
Error during ST communication
Change faulty module.
Bus termination error
There is no terminating plate or
there is a bad contact with the
module bus.
Install a terminating plate with in-
tegrated end bracket or insert the
base modules together correctly.
7.2
Display elements
Legend
LED on
LED off
7.2.1
Display elements for module diagnostics
The module has an LED for displaying module errors ("Err" LED).
Err
11
I0
21
I1
Err
LED
Meaning
Name
Colour
Status
Err
- - -
No error
Red
Module error