Function description
Operating Manual PSSu E S 2AI I se(-T)
21417-EN-04
20
Analogue value and typical digital value with a current range of 0 ... 20 mA, two's
complement:
Analogue value of cur-
rent
Decimal digital value
Binary digital value
Hexadecimal digital
value
0 mA
0
0000 0000 0000 0000
0000
H
10 mA
16 384
0100 0000 0000 0000
4000
H
20 mA
32 767
0111 1111 1111 1111
7FFF
H
Analogue value and typical digital value with a current range of 4 ... 20 mA, two's
complement:
Analogue value of cur-
rent
Decimal digital value
Binary digital value
Hexadecimal digital
value
4 mA
0
0000 0000 0000 0000
0000
H
12 mA
16 384
0100 0000 0000 0000
4000
H
20 mA
32 767
0111 1111 1111 1111
7FFF
H
4.3.5
Summary and overview
The module has the following configuration options:
Configurable properties
Default
value
Meaning
Input area
0
0 mA ... 20 mA
(1 = 4 mA ... 20 mA)
Manufacturer scaling active
1/TRUE
Activated
Manufacturer scaling offset
0
Offset: Magnitude 0
Manufacturer scaling gain
8194
D
8x amplification, displaced three bit places
User scaling active
0/FALSE
Deactivated
User scaling offset
0
Offset: Magnitude 0
User scaling gain
256
D
1x amplification, signal unchanged
Filter active
0/FALSE
Deactivated
Filter characteristic
0
2nd order FIR filter
Range monitoring active
1/TRUE
Activated
Upper limit value
4095
D
Upper limit of number range
Lower limit value
-4095
D
Lower limit of number range
Limit value 1 active
0/FALSE
Deactivated
Limit value 1
-32 767
D
Lower limit of number range
Limit value 2 active
0/FALSE
Deactivated
Limit value 2
32 767
D
Upper limit of number range
Sign and magnitude representa-
tion active
0/FALSE
Deactivated; two's complement is activated
Output ADC raw value only
0/FALSE
Deactivated