OPERATING MANUAL
PSEN op2H-A series
Manual start
Fig. 21 – Connection to safety relay – manual start
The diagrams show the connection between the safety light curtains and the safety relay
PNOZ s3 in automatic start mode (Fig. 20) and monitored manual start mode (Fig 21).
•
Avoid using varistors, RC circuits or LEDs in parallel to the relay inputs or in series
connection to the OSSD outputs.
•
The safety contacts of OSSD1 and OSSD2 may not be connected in series or in
parallel, but must be used separately (Fig. 22).
•
Should one of these configurations be used by mistake, the device switches to an
output error condition (see Chapter 8).
•
Connect both OSSDs outputs individually to the safety relay. Other configurations have
a negative effect on the safety of the system and are not permitted.
Fig. 22 – Correct OSSD signal load connection
Fig. 23 – Incorrect OSSD signal load
connection (I)
YES
NO
28
1003069-EN-03