PSEN ma1.4a-52
Operating Manual PSEN ma1.4a-52
22122-EN-06
19
Technical details
General
506321
506323
Approvals
CE, EAC (Eurasian), TÜV, cULus
Listed
CE, EAC (Eurasian), TÜV, cULus
Listed
Sensor's mode of operation
Magnetic
Magnetic
Coding level in accordance with EN
ISO 14119
Low
Low
Design in accordance with EN ISO
14119
4
4
Classification in accordance with
EN 60947-5-3
PDDB
PDDB
Electrical data
506321
506323
Supply voltage
Voltage
24 V
24 V
Kind
DC
DC
Voltage tolerance
-20 %/+20 %
-20 %/+20 %
Supply voltage
Max. current
200 mA
200 mA
Max. switching frequency
1 Hz
1 Hz
Lowest operating current (Im)
1 mA
1 mA
Switching voltage
24 V
24 V
Internal resistance
0 Ohm
0 Ohm
Max. switching current, safety con-
tacts
0,2 A
0,2 A
Max. breaking capacity, safety con-
tacts
5 W
5 W
Times
506321
506323
Reaction time (actuator removed)
2 ms
2 ms
Environmental data
506321
506323
Ambient temperature
Temperature range
-10 - 55 °C
-10 - 55 °C
Climatic suitability
In accordance with the standard
IEC 60068-2-30
IEC 60068-2-30
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Max. operating height above sea
level
2000 m
2000 m
EMC
EN 60947-5-3
EN 60947-5-3
Vibration
In accordance with the standard
EN 60947-5-2
EN 60947-5-2
Frequency
10 - 55 Hz
10 - 55 Hz
Amplitude
1 mm
1 mm
Shock stress
Acceleration
30g
30g
Duration
11 ms
11 ms