PSEN ma1.4a-52
Operating Manual PSEN ma1.4a-52
22122-EN-06
13
Examples for connection to Pilz evaluation devices:
I0
I1
PNOZmulti
PSENmag
3
1
2
4
T1
T0
PSEN ix1
3
1
2
4
11
12
13
14
brown
white
blue
black
Legend
I0
Input OSSD
I1
Input OSSD
T1, T2
Test pulse outputs
brown
white
blue
black
1
2
3
4
PSENmag
PSEN ix1
3
1
2
4
11
12
13
14
S21
S22
S11
S12
PNOZ s3
Installation
}
The unit can be installed in any position. However, safety switches and actuators must
be positioned opposite each other in parallel.
}
If possible, do not install the safety switch and actuator on to ferromagnetic material.
Changes to the operating distances are to be expected.
}
Safety switches and actuators should only be secured using M4 screws with a flat head
(e.g. M4 cheese-head or pan head screws). Use screws made of non-magnetic mater-
ial (e.g. brass).
CAUTION!
Potential loss of safety function due to changed device properties
The unit's properties may be affected if installed in an environment contain-
ing electrically or magnetically conductive material.
– Please check the operating distances and the assured release dis-
tance.