PSEN ma1.4a-52
Operating Manual PSEN ma1.4a-52
22122-EN-06
10
Wiring
Please note:
}
Information given in the
Technical details [
19]
must be followed.
}
Calculation of the max. cable length l
max
:
R
lmax
- R
i
R
l
/ km
I
max
=
R
lmax
= Max. overall cable resistance (see evaluation device's technical details)
Ri = Internal resistance sensor (see
Technical details [
19]
)
R
l
/ km = Cable resistance/km of the cable (see technical details cable)
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
}
In the following cases, check the function that detects shorts across contacts prior to
commissioning:
– On evaluation devices with DC supply voltage: Overall cable resistance ≥ 15 Ohms
per channel
– On evaluation devices with AC supply voltage: Overall cable resistance ≥ 25 Ohms
per channel
– For details of how to perform the test for shorts across the contacts, please refer to
the operating manual for the relevant evaluation device.
Pin assignment
NOTICE
The colour marking for the connection lead only applies for the cable that
Pilz supplies as an accessory
The safety switch is shown in an unoperated condition.
Layout of the 4-core cable
[1]
[2]
[3]
[4]
white
brown
blue
black
Requirements and connection to evaluation devices
For use of PSEN ma1.4a-52 in accordance with DIN EN 60947-5-3 an evaluation device
must be connected.
Connect the PSEN ma1.4a-52
}
either
with a certified Pilz evaluation device
}
or
with an evaluation device with defined properties