Operation
Operating Manual PNOZ s50
1002194EN02
50
Cat.
No.
Error message
Description
Remedy
0
2
Enter Stop
System is in "STOP" state
Purely for information
0
3
Enter Run
System is in "RUN" state
Purely for information
1
0
ACK IOFault
The "IOFault" error has been re
set with the inputs Y10/Y11 and/
or Y20/Y21 (1/0 pulse edge)
Purely for information
4
0
Copy Config
The configuration has been
loaded from the chip card to the
device.
Purely for information
4
1
Copy Config
The device has saved the config
uration to the chip card.
Purely for information
4
2
Missing Card
There is no chip card in the card
slot.
Insert a valid chip card into the
card slot
4
3
Invalid Card
The data on the chip card is in
valid
Check chip card
Insert a valid chip card into the
card slot
4
4
Mems. Differ
The data on the chip card differs
from the data in the device
Use a chip card containing the
device configuration
Write the device configuration to
chip card
4
5
Card Removed
The chip card has been removed
during operation
Insert a valid chip card into the
card slot
4
6
Unknown Card
The chip card does not contain
device data for the PNOZ s50
Insert a valid chip card into the
card slot
5
0
Wrong Pin
The password is invalid
Enter a valid password
5
1
Pin Changed
The password has been
changed
Purely for information
5
2
Count. at Max
The event counter has reached
the maximum value 99999999.
The event counter is not reset
automatically.
Reset event counter
5
3
Chan. Differ
Error in the device's parameter
settings
Check parameter settings
6
0
Supply NOK
Supply voltage B1/B2 to the
power circuits is outside the per
mitted range.
Parameter 1:
0x000000002
Check the supply voltage
6
1
Supply OK
Supply voltage B1/B2 to the
power circuits is once again
within the permitted range.
Parameter 1:
0x000000002
Purely for information
7
0
Reset Config
The device has been reset to its
default settings.
Purely for information