Commissioning
Operating Manual PNOZ s50
1002194EN02
29
WARNING!
Electric shock!
Safe electrical isolation must be ensured for the external power supply that
generates the supply voltage. Failure to do so could result in electric shock.
The power supplies must comply with EN 609501, 05/2006, EN 6155826,
11/1997.
INFORMATION
Max. current at the power circuits
It is essential to note that the effective current at terminals B1/B2 to supply
the power circuits must not exceed 10 A. The cables must be fitted with a
10 A fuse, characteristic B/C.
Supply voltage for power cir
cuits
Please note: The supply
voltage must be protected
with a fuse.
Fuse F1:
Circuit breaker 24 V, 48
VDC, 10 A, characteristic B/
C
L3
L1
L2
PE
B1
B2
L+
L-
F1
6.1.5
Power circuit
Power circuit
Dualpole outputs
O1+
O1-
O2+
O2-