Relay outputs
750111
751111
External contact fuse protection,
auxiliary contacts
Max. melting integral
160 A²s
160 A²s
Blow-out fuse, quick
10 A
10 A
Blow-out fuse, slow
6 A
6 A
Blow-out fuse, gG
6 A
6 A
Circuit breaker 24 V AC/DC,
characteristic B/C
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au
Conventional thermal current
while loading several contacts
750111
751111
Ith per contact at UB DC;
AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-
tact
6 A
6 A
Conv. therm. current with 2 con-
tacts
6 A
6 A
Conv. therm. current with 3 con-
tacts
6 A
6 A
Conv. therm. current with 4 con-
tacts
6 A
6 A
Conv. therm. current with 5 con-
tacts
6 A
6 A
Conv. therm. current with 6 con-
tacts
5,7 A
5,7 A
Conv. therm. current with 7 con-
tacts
5,3 A
5,3 A
Conv. therm. current with 8 con-
tacts
5 A
5 A
Times
750111
751111
Switch-on delay
With automatic start after power
on typ.
30 ms
30 ms
With automatic start after power
on max.
50 ms
50 ms
Delay-on de-energisation
With E-STOP typ.
18 ms
18 ms
With E-STOP max.
30 ms
30 ms
With power failure typ.
18 ms
18 ms
With power failure max.
30 ms
30 ms
Environmental data
750111
751111
Climatic suitability
EN 60068-2-78
EN 60068-2-78
Ambient temperature
Temperature range
-10 - 55 °C
-10 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
-40 - 85 °C