PNOZ s11
Operating Manual PNOZ s11
21693-EN-11
| 17
Relay outputs
750111
751111
Utilisation category of auxiliary con-
tacts
AC1 at
240 V
240 V
Min. current
0,003 A
0,003 A
Max. current
6 A
6 A
Min. output
0,04 VA
0,04 VA
Max. power
1500 VA
1500 VA
DC1 at
24 V
24 V
Min. current
0,003 A
0,003 A
Max. current
6 A
6 A
Min. output
0,04 W
0,04 W
Max. power
150 W
150 W
Utilisation category
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at
230 V
230 V
Max. current
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
5 A
5 A
Utilisation category of auxiliary con-
tacts
AC15 at
230 V
230 V
Max. current
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
5 A
5 A
Utilisation category in accordance
with UL
Voltage
240 V AC G.U. (same polarity)
240 V AC G.U. (same polarity)
With current
6 A
6 A
Voltage
24 V DC G. U.
24 V DC G. U.
With current
6 A
6 A
External contact fuse protection,
safety contacts
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Max. melting integral
260 A²s
260 A²s
Blow-out fuse, quick
10 A
10 A
Blow-out fuse, slow
6 A
6 A
Blow-out fuse, gG
10 A
10 A
Circuit breaker 24V AC/DC,
characteristic B/C
6 A
6 A