Commissioning
Operating Manual PNOZ m ES EtherCAT
1003057-EN-04
15
6.3
Interface assignment
RJ45 socket
8-pin
PIN
Standard
8 1
1
TD+ (T)
2
TD- (Transmit-)
3
RD+ ()
4
n.c.
5
n.c.
6
RD- (Receive-)
7
n.c.
8
n.c.
n.c.: Not connected
6.4
Download modified project to the PNOZmulti safety system
As soon as an additional expansion module has been connected to the system, the project
must be amended using the PNOZmulti Configurator. Proceed as described in the operat-
ing instructions for the base unit.
NOTICE
For the commissioning and after every program change, you must check
whether the safety devices are functioning correctly.
6.5
Preparing for operation
}
Install Device Description File
Install the
Device Description File
in your configuration software. You can only then use
the PNOZ m ES EtherCAT.
}
Connect the supply voltage to the base unit:
Terminals
24 V
and
A1 (+)
: + 24 VDC
Terminals
0 V
and
A2 (-)
: 0 V