Technical details
Operating Manual PNOZ m ES EtherCAT
1003057-EN-04
19
8
Technical details
General
Approvals
CE, EAC (Eurasian), cULus Listed
Electrical data
Supply voltage
for
Module supply
Voltage
24 V
Kind
DC
Voltage tolerance
-20 %/+25 %
Max. continuous current that the external power
supply must provide
35 mA
Output of external power supply (DC)
0,9 W
Potential isolation
yes
Supply voltage
for
Module supply
internal
Via base unit
Voltage
3,3 V
Kind
DC
Current consumption
60 mA
Power consumption
0,2 W
Max. power dissipation of module
1,5 W
Status indicator
LED
Fieldbus interface
Fieldbus interface
EtherCAT
Device type
Slave
Log
CANopen over EtherCAT
Transmission rates
100 MBit/s
Connection
RJ45
Galvanic isolation
yes
Environmental data
Ambient temperature
In accordance with the standard
EN 60068-2-14
Temperature range
0 - 60 °C
Forced convection in control cabinet off
55 °C
Storage temperature
In accordance with the standard
EN 60068-2-1/-2
Temperature range
-25 - 70 °C
Climatic suitability
In accordance with the standard
EN 60068-2-30, EN 60068-2-78
Condensation during operation
Not permitted
Max. operating height above sea level
2000 m
EMC
EN 61131-2