Operation
Operating Manual PIT m4SEU
1004648-EN-02
| 59
8.6
Troubleshooting
If an error occurs on the PIT m4SEU, the last operating mode to be set will be retained.
Error
Possible cause
Remedy
Unable to switch the op-
erating mode
Multiple pushbuttons oper-
ated
Make sure that only one push-
button is operated
Operating time too long or
too short
Make sure that the period of op-
eration is observed
Transponder key is not de-
tected
Make sure that the transponder
key on the PITreader is inserted
correctly
No valid permission
Make sure that you use a
transponder key that has the re-
quired permission.
Ensure that the PITreader inter-
face is connected correctly.
See also the PITreader operat-
ing manual.
Device error
- The DIP switch setting was
changed during operation
- Invalid configuration via the
DIP switch setting
Please refer to the timing diagram for
8.6.1
Delete error
Procedure:
}
Switch off device (power off)
}
Configure DIP switch setting as shown (all switches to ON)
4 3 2 1
Off
On
}
Device restart → device error is still displayed
}
Switch off device
}
Configure required DIP switch position
}
Device restart → Error deleted
8.7
Diagnostics
Status information is sent to the interface for status information (SIo0 … SIo3) and to the
PITreader.
8.7.1
Status information about the interface for status information
Various status information can be signalled via the interface for status information (see
). The status information can be evaluated through a control system
Interface for status information [
).