Commissioning
Operating Manual PNOZ s30
1001715-EN-15
50
6.2.7.2
Basic settings Ini pnp pnp
Settings for basic configuration 1
Level
Designation
on the display
Description
Settings
1
Basic Parameter
Ini pnp pnp
Default
Load?
Select the default settings with
which the basic configuration
menu
Ini pnp pnp
is to be called:
-Load : The basic parameters are
loaded. Then it switches to the ba-
sic menu
Ini pnp pnp
.
The basic parameters should al-
ways be loaded when commis-
sioning for the first time.
- Edit: The basic parameters are
not loaded, i.e. all parameters are
retained. The basic menu para-
meters can be changed within the
permitted boundaries.
- Escape: Exits the basic menu.
2
Standstill
Rel.1 Out 1
Default
2.00 Hz
Enter standstill frequency
100 mHz ... 10.0 Hz
2
v max
Rel.2 Out 2
Default
500 Hz
Enter the max. permitted speed
10 mHz ... 3.00 kHz
Other, pre-defined settings:
}
Encoder type
2 pnp type proximity switches
}
Parameter set/select input
P0, select inputs are ignored (Select inputs mode: "None")
}
Hysteresis
Standstill and speed, 2 % each
}
Output assignment
–
Standstill: Relay output Rel.1 and semiconductor output Out 1
–
Speed: Relay output Rel.2 and semiconductor output Out 2
}
Start mode
–
Rel.1 and semiconductor output Out 1, Rel.2 , Out 1, Out 2: Automatic start "Auto-
matic"