Commissioning
Operating Manual PNOZ s30
1001715-EN-15
44
6.2.4
Password protection
The configuration is protected through passwords. There is a master password and a cus-
tomer password.
Factory setting for both passwords: 0000
The password levels contain different authorisations:
}
Master password
Display: All settings
Edit: All settings
}
Customer password
Display: All settings
Edit:
–
The customer password can be changed.
–
The language can be changed.
–
The settings can be reset to the factory settings.
}
No password
Edit:
–
The language can be changed.
–
The settings can be reset to the factory settings.
If the settings are reset to the factory settings, the passwords and the language will also be
reset to the factory settings.
The passwords can be changed at any time in the menu.
Enter a password containing 4 characters.
6.2.5
Use chip card
The parameters that are set on a unit can be stored on the chip card. The data is stored
along with a device identifier, the passwords, the name of the configuration and the check
sum. We recommend that you
always
operate the unit with a chip card.
}
If the parameters on a device have been changed due to an error, they can be restored
using the backup copy on the chip card.
}
If a unit requires maintenance or needs to be exchanged, the chip card can be used to
download the parameters to another unit.
INFORMATION
If you operate the unit without a chip card, the "Fault" LED will light and the
following message will appear once only:
Please Insert SIM Card!
. If you
change the parameters, the
Please Insert SIM Card!
message will re-
appear.