PIKA B801 REcharge Скачать руководство пользователя страница 32

29 

 

Unit displays waiting state  

1)

 

Some fault conditions warrant a timeout, if the unit 
does not return to normal operation after 10 
minutes contact technical service. 

LCD  Screen  displays  solid  black  or  solid 
white 

1)

 

Turn  the  unit  off  using  the  power  switch  on  the 
bottom, wait 1 minute and turn it back on again.  

2)

 

If  operating  in  cold  temperatures  the  LCD  may  be 
slow  to  respond  but  will  increase  responsiveness 
once warmed up.  

Charge  controller  display  does  not  show 
connected REbus

™  devices  OR  connected  

devices  have  status  “offline”  although  the  

charge controller is operating. 

1)

 

Check  that  ground  wire  on  REbus

™   side   is  

connected  to  the  lug  in  the  wiring  compartment. 
There  must  be  a continuous  ground wire  from  the 
B801  to  the  device  for  communications  to  work 
properly. 

2)

 

Reseat  the  cable  that  attaches  the  LCD  screen  to 
the  main  board  within  the  B801.  Note  this  is  a 
polarized  connector.  It  may  be  dislodged  during 
shipping or installation.  

3)

 

Call technical support for further troubleshooting. 

Charge  controller  shows  devices  that  are 
no longer connected to REbus

TM

 

1)

 

Delete  unwanted  or  disconnected  devices  by 

selecting  “Remove”  un

der the device page. Devices 

are automatically discovered but must be manually 
removed. 

Devices  on 

REbus™

  (turbine,  PV,  etc)  are 

shutting down frequently (multiple times 
a day) 

1)

 

Check  the  battery  voltage  of  your  system,  the 
batteries may be fully charged and the  devices 
are  limiting  their  power  output  as  to  not 
overcharge the batteries.  

2)

 

A  generator or other  source  is  pushing  battery 
voltage  high  causing  the 

REbus™

  devices  to 

limit their output power.  

Charger will not come out of low battery 
voltage state 

1)

 

Check to ensure the B801 is configured for the 
appropriate battery bank voltage 

2)

 

Verify batteries are not damaged by measuring 
voltage with a multimeter  

The  B801  is  showing  a  different  battery 
voltage  than  other  hardware  I  have  on 
my system. 

1)

 

Calibration  between  different  manufacturers 
may  vary.  Ensure  wires  to  the  batteries  are  as 
short as possible and connections are tight. 

2)

 

Verify  battery  voltage  with  a  calibrated 
voltmeter and adjust hardware to match it.   

 

 

 

 

 

Содержание B801 REcharge

Страница 1: ...Pika B801 REcharge Off grid Charge Controller Operation Manual...

Страница 2: ......

Страница 3: ...Operation Manual B801 Bidirectional REbus Battery Charge Controller Revision Table Revision Date Changes 1 0 03 19 2015 Initial Release...

Страница 4: ...on gateway enabling monitoring and control of your entire renewable energy system Unlike conventional charge controllers which only connect to one type of energy source Pika s B801 is designed to oper...

Страница 5: ...vice 6 4 The REbusTM Microgrid 7 4 1 Simple and Efficient Power Distribution and Management 7 4 2 Integrated Power Line Carrier PLC Communications 7 4 3 REbus Control Protocol RCP 7 5 Designing a REbu...

Страница 6: ...peration 19 7 7 Configurations 19 8 Internet Compatibility 22 8 1 Wi Fi Antenna 22 8 2 Configuring your Wi Fi Connection 23 8 2 1 Scan based network setup 23 8 2 2 Add network setup 24 8 3 Wi Fi Statu...

Страница 7: ...efully read and follow all instructions cautions and warnings in this user manual Store this manual so that it is always easily accessible 1 1 Symbols used in this document WARNING This indicates a fa...

Страница 8: ...o the charge controller installation manual for detailed information about the product and its intended use The charge controller may only be operated with REbus devices Do not use the charge controll...

Страница 9: ...l necessary permits and agreements from your local government and your utility company for a legal and code compliant installation of your REbus Smart Microgrid system See the User Manual for more det...

Страница 10: ...e REbusTM Microgrid is designed to support many different types of renewable energy sources and power converters as well as accommodating future 380VDC REbusTM Microgrid loads that are presently in de...

Страница 11: ...terface 6 1 Overview of User Interface The B801 Charge Controller user interface is accessible via the LCD on the front cover It is designed to provide basic information such as power energy and batte...

Страница 12: ...his blue LED is illuminated when a connection to a Wi Fi router has been established and is operating normally The blue LED is OFF if no Wi Fi connection has been established 6 3 LCD Display The LCD d...

Страница 13: ...grid The color of the LED does not depend on the page that is currently displayed E User Input buttons These five buttons allow the user to scroll through display pages and command connected devices a...

Страница 14: ...s Discharging Battery The B801 is exporting power to the REbusTM DC Microgrid Equalize Charging Battery The B801 is performing an equalize cycle on the batteries as initiated by the user ERR General A...

Страница 15: ...harge Controller page Always configure the B801 before Enabling it Press the center button to access the various options for the charge controller From here use the arrows keys to navigate The B801 ma...

Страница 16: ...If making changes to battery chemistry or number of cells commit changes and re enter the settings menu from the B801 device page before configuring the rest of the setpoints as described below To sa...

Страница 17: ...criptions of the connection status messages and troubleshooting information C Wi Fi activity LED This blue LED will flash when the B801 is communicating on a Wi Fi network D Wi Fi settings not configu...

Страница 18: ...Status Indicator LED This LED describes the state of all of the REbusTM devices connected to the REbusTM The LED will be RED if one or more REbusTM devices are reporting an error YELLOW if no REbusTM...

Страница 19: ...are providing power to the REbus DC microgrid Always check for voltage on each terminal before performing any electrical service 7 3 Enable Disable Enable To permit the B801 to import and export powe...

Страница 20: ...unt of current into the batteries After an allotted time has elapsed the current will have decreased significantly and charging will then enter Float charging stage at this point the batteries are nea...

Страница 21: ...s are depleted to the point where they may be damaged rendering them unusable if they are discharged any further Please check with the battery manufacturer about extremely low voltage conditions for y...

Страница 22: ...designed with a number of user configurable options allowing customization for various battery chemistries and voltages Recommended default setting are preprogramed into the B801 Setpoints should only...

Страница 23: ...mistry Select 0 for custom batteries 1 for flooded lead acid 2 for Gel cell batteries and 3 for AGM lead acid batteries After changing this setpoint a default set of values for the chosen battery chem...

Страница 24: ...he B801 will still source power to loads Below this voltage the B801 will enter a hibernation state see Low Battery Time Off and Low Battery Time On setpoint descriptions for more details 13 Absolute...

Страница 25: ...the LCD screen Note that in order to receive firmware upgrades and to use the Pika REview online monitoring system See section 8 4 Pika account and the REview online monitoring system you must be con...

Страница 26: ...nually For most networks using DHCP simply scan enter the network password and connect If manual configuration is desired selected the Advanced option select Manual and enter an IP address Subnet Mask...

Страница 27: ...and DOWN to select and CENTER to perform the highlighted item Manual Step 4 Enter your network type If your network is secured with a password consult your wireless network router to determine whethe...

Страница 28: ...ection If this fails to happen the status Offline will be displayed on the B801 on your REview page If your network name and password haven t changed simply power cycle the B801 using the switch on th...

Страница 29: ...sources of 2 4 GHz radio If this happens repeatedly try moving your Wi Fi router closer to the B801 Connection failed Security mismatch This message will be displayed if the B801 has been configured...

Страница 30: ...ration on the B801 Conn permanently lost Disassociate received This message indicates that your Wi Fi router has told the B801 to repeatedly reconnect This indicates an unusual authorization issue bet...

Страница 31: ...oubleshooting the issue 10 Troubleshooting Guide Refer to the table below for guidance on how to troubleshoot your B801 If you are experiencing a symptom not addressed in this guide or require further...

Страница 32: ...hnical support for further troubleshooting Charge controller shows devices that are no longer connected to REbusTM 1 Delete unwanted or disconnected devices by selecting Remove under the device page D...

Страница 33: ...dware visit http profiles pika energy com Collect all device ID cards which will be needed for registration Consult the REview quickstart guide for more information regarding registration If you have...

Страница 34: ...ontinuous DC discharging battery current 80 A Maximum continuous DC charging power at 50C 4000 W Maximum continuous DC discharging power at 50C 2800 W Ambient temperature 20 60 C Full power operation...

Страница 35: ...32...

Отзывы: