9
When solid green, the B801 is functioning normally and is importing or exporting power to/from the
REbus™
DC Microgrid. Blinking green indicates a state where the B801 is functioning normally but not
importing or exporting power to/from the
REbus™
DC Microgrid. When solid yellow, the B801 is in a
“Waiting” state, no power is being imported/exported and no user input is required.
After a timeout
has expired the B801 will exit “W
aiting
”
state and resume normal operation. When solid red, an error
with the charge controller has been detected and user attention is required before the unit will resume
operation. See the LCD Display for more information about the specific error that has been detected.
Blinking red is displayed during an equalization cycle which is initiated by the user. Reference Section
6.3.2 for a table of
Error! Reference source not found.
.
6.2.3 Blue “Wi
-
Fi” LED
This blue LED is illuminated when a connection to a Wi-Fi router has been established and is operating
normally. The blue LED is OFF if no Wi-Fi connection has been established.
6.3 LCD Display
The LCD d
isplay provides access to information about the B801 and other connected REbus™ devices.
The display is organized into pages with three default pages and one additional page for each attached
REbus™ device
. Each device page allows the user to enable/disable the device. Additionally, user
adjustable setpoints can be accessed using the LCD display.
6.3.1 REbus™ System Page
The REbus™ System
Page gives an overview of the entire REbus™
DC Microgrid (displays voltage and DC
power). This is the default page of the display and appears automatically on power up.
Position
Description Explanation
A
REbus
TM
DC
Power
The instantaneous power being generated by REbus
TM
sources. This is the
amount of power being input into the REbus
TM
side of the B801.
B
Bus Voltage The voltage of the electrical bus that connects all of the REbus
TM
devices to the
B801. The normal range is 340 to 410 Volts.