13
Holding the up or down button for 5 seconds will increment the setpoint much faster. Refer to
for a description of each setpoint as well as permissible ranges. Only after pressing
“Commit” will all of the
setpoints be saved.
NOTE
that changing the
number of cells (“
Batt Num Cell
”,
setpoint #4) or the battery chemistry ty
pe (“
Batt Type
”, set
point #3) will automatically default the
ENTIRE
setpoint table after selecting
commit
. Any alteration to battery chemistry or number of cells in
the setpoint table will cause the remainder of the table to default to different values. If making changes
to battery chemistry or number of cells, commit changes and re-enter the settings menu from the B801
device page before configuring the rest of the setpoints as described below.
To save time during initial B801 configuration, follow the steps below:
1. Navigate to
settings
from the B801 device page, select “Modify”. This brings up the menu to edit the
setpoints.
2. Select the correct battery type and number of cells (according to Table 1 User Setpoint Table)
3. Commit battery type and number of cells (scroll to bottom of menu, select
“
commit
”
and press center
button)
4. Re-navigate to
settings
from the B801 device page,
select “Modify”
and configure all other B801
setpoints
5.
Commit the setpoints by scrolling to the bottom of the menu, selecting “commit”
by pressing the
center button.