![Phoenix Contact AXC F 1152 Скачать руководство пользователя страница 103](http://html1.mh-extra.com/html/phoenix-contact/axc-f-1152/axc-f-1152_installing-starting-up-and-operating_1551419103.webp)
Use of the AXC F 2152 controller under extreme ambient conditions
107708_en_08
PHOENIX CONTACT
103 / 113
A 4
Use of the AXC F 2152 controller under extreme
ambient conditions
The AXC F 2152 controller has been tested successfully over 250
temperature change cy-
cles in accordance with IEC 61131-2 in the range from -40°C to +70°C.
The following conditions were observed:
–
The Axioline F devices for all connecting cables were connected with a minimum con-
ductor cross section of 0.5 mm²
–
The Axioline F station was assembled on a wall-mounted horizontal DIN rail
–
Fans were used to ensure continuous movement of air in the control cabinet
–
The Axioline F station was not exposed to vibration or shock
–
The Axioline F station was operated with a maximum of 24.5 V (ensured by using
regulated power supply units)
Figure 14-1
Temperature change cycle
Temperature in the control cabinet/ambient temperature