Asymmetric ground system (corner grounded TN systems)
In the following four situations, you must remove the IT jumper. This is to prevent the system
from grounding through the RFI and filter capacitors and damaging the CONTACTRON
Speed Starter.
Figure 5-10
Grounding at a corner in a triangle configuration
Figure 5-11
Grounding at a midpoint in a polygonal configuration
CAUTION:
Do not remove the IT jumper while power to the input terminal of the CONTACTRON
Speed Starter is ON.
NOTE:
You must remove the IT jumper for an asymmetric ground system.
L2
L3
L1
L2
L3
L1
Содержание 1201132
Страница 1: ...User manual CONTACTRON Speed Starter...
Страница 14: ...CONTACTRON Speed Starter 14 146 PHOENIX CONTACT 109908_en_00...
Страница 18: ...CONTACTRON Speed Starter 18 146 PHOENIX CONTACT 109908_en_00...
Страница 24: ...CONTACTRON Speed Starter 24 146 PHOENIX CONTACT 109908_en_00...
Страница 46: ...CONTACTRON Speed Starter 46 146 PHOENIX CONTACT 109908_en_00...
Страница 48: ...CONTACTRON Speed Starter 48 146 PHOENIX CONTACT 109908_en_00...
Страница 86: ...CONTACTRON Speed Starter 86 146 PHOENIX CONTACT 109908_en_00...
Страница 90: ...CONTACTRON Speed Starter 90 146 PHOENIX CONTACT 109908_en_00...
Страница 106: ...CONTACTRON Speed Starter 106 146 PHOENIX CONTACT 109908_en_00...
Страница 108: ...CONTACTRON Speed Starter 108 146 PHOENIX CONTACT 109908_en_00 14 1 2 3 phase...
Страница 112: ...CONTACTRON Speed Starter 112 146 PHOENIX CONTACT 109908_en_00 14 3 Block diagram 14 3 1 1 phase...
Страница 113: ...Application notes 109908_en_00 PHOENIX CONTACT 113 146 14 3 2 3 phase...
Страница 114: ...CONTACTRON Speed Starter 114 146 PHOENIX CONTACT 109908_en_00...
Страница 132: ...CONTACTRON Speed Starter 132 146 PHOENIX CONTACT 109908_en_00...
Страница 136: ...CONTACTRON Speed Starter 136 146 PHOENIX CONTACT 109908_en_00...
Страница 140: ...CONTACTRON Speed Starter 140 146 PHOENIX CONTACT 109908_en_00...
Страница 147: ......