Startup
110146_en_00
PHOENIX CONTACT
83 / 128
7.2
Startup with PLCnext Engineer
Please note:
Startup for the operation of a redundant control system with two controllers is de
-
scribed below.
If you are operating your application with just one controller (“SingleMode” redundan
-
cy status), the startup steps are the same.
For startup in PLCnext Engineer, program the controller that manages the process (PRI
-
MARY controller).
Only
the PRIMARY controller is therefore visible in the
PLCnext Engineer application. After you have successfully compiled the PLCnext Engineer
application and transferred it to the PRIMARY controller, the PRIMARY and BACKUP con
-
trollers are synchronized with each other via the device’s internal SYNC interface. The
BACKUP controller will be started up automatically.
Please note
:
For the PRIMARY and BACKUP controllers to synchronize with each other, the follow
-
ing requirements must be met:
– Redundancy type “First” has been assigned to one of the controllers and redun
-
dancy type “Second” has been assigned to the other controller.
–
The controllers are connected together via the SYNC interface.
7.2.1
Installing PLCnext Engineer
The software can be downloaded at
phoenixcontact.net/product/1046008
.
•
Download the software (version ≥ 2022.0 LTS) onto your PC.
•
Double-click the *.exe file to start installation.
•
Follow the instructions in the installation wizard.