RFC 4072R
60 / 128
PHOENIX CONTACT
110146_en_00
4.11.7.2
“SETTINGS” submenu
Figure 4
-
44
“Redundancy” menu, “REDUNDANCY DETAILS” submenu, “SETTINGS”
submenu
The redundancy type that is currently set for the controller is displayed locally in the “SET
-
TINGS” submenu. You can use
and
to modify the redundancy type of controller.
Possible settings:
– “None” (the redundancy functionality is deactivated).
– “First”
– “Second”
Modifying the redundancy
type
To modify the redundancy type of the controller, proceed as follows:
•
Tap
or
until the desired redundancy type is displayed.
•
To save the modified setting, tap
.
⇒
The message “Redundancy Type changed. Restart!” appears in the display.
Figure 4
-
45
Message “Redundancy Type changed. Restart!”
The message “Redundancy Type changed. Restart!” disappears automatically. You are
then returned to the “REDUNDANCY DETAILS” submenu.
The modified setting will not take effect until the controller has been restarted.
•
Restart the controller.