Dynalite Hardware
.......................................
Installation Guide
.......................................
Page 11
.......................................
14
th
November 2019
www.philips.com/dynalite
Installing sensors
Motion detection positioning
C
A single Dynalite sensor can perform motion detection, light regulation and IR receive simultaneously.
C
Typical detection range is measured at
≤
25
°
C (77
°
F). Range is reduced at higher temperatures.
C
Sensors must receive specified supply voltage (12-18 V or 20-26 V) from the DyNet network. If necessary,
add a network power supply to ensure adequate network voltages during day to day fluctuations.
Position sensor to detect motion in the specified area:
1.
Install correct sensor type for location and application
(wall or ceiling mounted, PE, PIR, ultrasonic, high bay, outdoor)
2.
Ensure correct orientation for long and short field of view.
3.
Install sensor out of direct sunlight.
4.
Install sensor away from air conditioning vents and sources of electromagnetic interference.
5.
Lift inbuilt mask where applicable, to limit sensor detection area.
Lights trigger only upon entry
Using detection area mask
May trigger from passersby