72 |
P a g e
Table 21
– Fault Codes
TEXT MESSAGE
DESCRIPTION / COMMENTS
NOTES
OUTPUT FAULT
Check for short circuit on output lines and load. Contact factory
1
OVER TEMPERATURE
Internal temperature of the drive exceeded safe limits. Check fans and ventilation
openings for obstruction. Reduce ambient temperature.
2
BUS OVERVOLTAGE
Sudden and severe regenerative power under high line voltage conditions may result in
bus overvoltage. Check line voltage or increase ramp up and ramp down times.
2
PRECHARGE FAIL
DC bus voltage did not reach normal level. Possible failure of input diode.
3
HIGH INPUT VOLTAGE
Input voltage has exceeded a level for safe operation. Reduce input voltage. General
purpose buck/boost transformers are compatible with 1LH Series drives.
2
MOTOR OVERLOAD
Output current has exceeded the value set for
OVERCURRENT LIMT
in OPERATING
PARAMETERS menu. Check status of motor load. If output current limit is increased,
make sure it is within the limit of the motor nameplate. Automatic restarts are set by
RESTART DELAY 1
and
RESTARTS CUR OVL
in the AUTO RESTART
PARAMETERS menu.
P, 2
CURRENT UNBALANCED
Motor current unbalance has exceeded the limit set in
CURRENT UNBALANC
under
CHANGE PARAMETER VALUES menu. Check motor load for normal operation, or
increase current unbalance limit.
P, 2
DRY WELL KW
Real power in kW consumed by the motor load has fallen below the limit set in
MINIMUM POWER under CHANGE PARAMETER VALUES menu. Commonly used to
detect dry well condition.
P, 2
DRY WELL CURRENT
Motor current has fallen below the value set in
UNDERCURRENT LIM
Commonly used
to detect dry well condition.
P, 2
OUTPUT OVERLOAD
Indicates a large and sudden overcurrent event on the output module. Check the motor
circuit for faults. Sudden changes in the load may also have occurred such as the
closing of a relay that results in an across-the-line start of a motor. Never install relays in
the motor circuit.
1
LOW INPUT VOLTAGE
Input voltage has fallen below a level for safe operation of the drive.
2
GROUND FAULT
A fault between an output line and earth has been detected. Immediately disconnect
input power and check output lines with a megger to verify a fault. Nuisance trip is a
possibility. Sensitivity of fault detection can be adjusted by the Operating Parameter
GND FAULT DETECT
. See
for details.
1
SENSOR CONNECTION FAIL
Indicates open circuit. 4-20mA analog signal is not present on Control Terminals I_1 and
I_2. This could indicate failure of the 4-20mA sensor or that the cables from the sensors
have been disconnected.
2
15V DC POWER OVERLOAD
Indicates closed circuit. Check for short circuit between lines. Check the polarity of the
wires on I_1+ and I_1- .
1
BROKEN PIPE FAULT
Broken Pipe fault. Indicates the possibility of a broken pipe.
1
AUX1 Latch Fault
Switch connected to AUX1 input has opened. Drive will remain off until fault is cleared.
No auto restart allowed. See
AUX1 SELECT
P,1
AUX2 Latch Fault
Switch connected to AUX2 input has opened. Drive will remain off until fault is cleared.
No auto restart allowed. See
AUX2 SELECT
P,1
P = Fault may be related to an adjustable parameter. Always check the value of the parameter to eliminate nuisance
tripping.
1 = Drive has shut down due to a potentially dangerous condition. Drive will remain OFF until input power is cycled
OFF/ON. Use caution if the drive is restarted.
2 =
WARNING:
Auto restart allowed for this fault. Motor may restart automatically without warning after a fault
when operating conditions permit. Make certain input power is disconnected before servicing the unit or its
connected loads.
Содержание 2XD Series
Страница 10: ...4 P a g e 2 3 Dimensional Drawings Figure 5 SD Series Line Drawing...
Страница 11: ...5 P a g e Figure 6 SD Series Line Drawing if selected with optional breaker see Figure 9...
Страница 12: ...6 P a g e Figure 7 SD Series Line Drawing if selected with optional breaker see Figure 9...
Страница 13: ...7 P a g e Figure 8 SD Series Line Drawing if selected with optional breaker see Figure 9 or Figure 10...
Страница 14: ...8 P a g e Figure 9 SD Series Line Drawing...
Страница 15: ...9 P a g e Figure 10 SD Series Line Drawing...
Страница 16: ...10 P a g e Figure 11 2XD Series Line Drawing...
Страница 80: ...74 P a g e Figure 36 SW1 in SD Systems...